33
CHAPTER 3 SPECIFICATIONS
3
3.
1 G
eneral
S
pecif
ic
at
ions
CHAPTER 3
SPECIFICATIONS
This chapter describes the specifications of the temperature control module.
3.1
General Specifications
*1
Do not use or store the temperature control module under pressure higher than the atmospheric pressure of altitude 0m.
Doing so may cause malfunction. When using the temperature control module under pressure, please consult your local
Mitsubishi representative.
*2
If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the
module can be used even outside the control panel.
*3
This indicates the section of the power supply to which the equipment is assumed to be connected between the public
electrical power distribution network and the machinery within premises. Category II applies to equipment for which
electrical power is supplied from fixed facilities. The surge voltage withstand level for the equipment with the rated
voltage of 300V or less is 2500V.
*4
This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used. Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by
condensing must be expected occasionally.
To use the temperature control module complying with the EMC Directive, refer to the following.
Item
Specifications
Operating ambient
temperature
0 to 55
Storage ambient
temperature
-25 to 75
Operating ambient
humidity
5 to 95%RF, non-condensing
Storage ambient
humidity
Vibration resistance
Compliant with JIS
B 3502 and IEC
61131-2
Frequency
Constant
acceleration
Half amplitude
Number of sweeps
Under intermittent
vibration
5 to 8.4Hz
3.5mm
10 times each in X,
Y, and Z directions
8.4 to 150Hz
9.8m/s
2
Under continuous
vibration
5 to 8.4Hz
1.75mm
8.4 to 150Hz
4.9m/s
2
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 (147m/s
2
, 3 times each in X, Y, and Z directions)
Operating
atmosphere
No corrosive gases
Operating altitude
0 to 2000m
Installation location
Inside a control panel
Overvoltage
category
II or less
Pollution degree
2 or less
Equipment class
Class I