CHAPTER 8 FUNCTIONS
8
8.
1 Com
m
on F
unc
tions
8.1.6
Auto-setting at input range change
When an input range is changed, using this function automatically changes related parameter data to prevent an error
outside the setting range. Set the function under Auto-setting at input range change (address: 1H. b0).
The following is the setting timing.
The sampling cycle differs depending on the setting of "Sampling cycle selection". (
(1) Remote buffer memory automatically set
For the applicable remote buffer memory, refer to the following.
(2) Setting method
1.
Set "Method selection" to "Param write (Station parameter)".
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "1: Enable" for "Auto-setting at input range change".
Common
Sampling cycle
Recognition
OFF
OFF
ON
ON
Before change
After change
Setting by a user
Value that has been
automatically changed
Recognition
250ms or 500ms
250ms or 500ms
250ms or 500ms
Controlled by the program
CH□ Input range
(address: 100H, 130H, 160H, 190H)
At the start of processing performed every
250ms or 500ms, the module recognizes
values of an output signal and remote
buffer memory area.
If necessary, change the value of remote buffer memory
area that has been automatically set at the end of the
processing, and turn on and off Initial data setting
request flag (RY9).
Initial data setting request flag (RY9)
Remote buffer memory area where
a value is automatically set
Initial data setting completed flag (RX9)
Controlled by the temperature control module