background image

e n

6

4-1. PURGING PROCEDURES AND LEA  TEST

1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe. 

(The stop valves are fully closed and covered in caps in their initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of stop valve 

on the gas pipe side of the outdoor unit.

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)

4) Check the vacuum  ith gauge manifold valve, then close gauge manifold 

valve, and stop the vacuum pump.

5) Leave as it is for one or t o minutes. Make sure the pointer of gauge manifold 

valve remains in the same position. Confirm that pressure gauge sho s 

14.7  

psi [Gauge] (

0.101 MPa).

6) Remove gauge manifold valve quickly from service port of stop valve.

7) After refrigerant pipes are connected and evacuated, fully open the valve stem 

of all stop valves on both sides of gas pipe and liquid pipe by the hexagonal 

rench. If the valve stem hits the stopper, do not turn it any further. Operating 

w ithout fully  opening low ers the performance and this causes trouble.

8) Refer to 1-2., and charge the prescribed amount of refrigerant if needed. Be 

sure to charge slow ly  w ith liquid refrigerant. Otherw ise, composition of the 
refrigerant in the syst em may  be changed and affect performance of the air 
conditioner.

9) Tighten cap of service port to obtain the initial status.

10

) Leak test

4-2. GAS CHARGE

Perform gas charge to unit.

1) Connect gas cylinder to the service port of stop valve.

2) Perform air purge of the pipe (or hose) coming from refrigerant gas cyl inder.

3) Replenish specified amount of the refrigerant,  hile operating the air conditioner for cooling.

N o t e :

In case of adding refrigerant, comply  ith the quantity specified for the refrigerating cycle.

CAUTION

When charging the refrigerant syst em w ith additional refrigerant, be sure to use liquid refrigerant. 
Adding gas refrigerant may  change the composition of the refrigerant in the syst em and affect 
normal operation of the air conditioner. Also, charge the liquid refrigerant slow ly , otherw ise the 

compressor  ill be locked.

To maintain the high pressure of the gas cyl inder, w arm the gas cyl inder w ith w arm w ater (under 

104°F (40°C)) during cold season. But never use naked fire or steam.

Gauge mani-

fold valve (for 

R410A)

Compound pressure 
gauge (for R410A)

–14.7  psi
(–0.101MPa)

Handle 
Low

Handle High

Vacuum pump

(for R410A)

Charge hose 
(for R410A)

Close

Open

Hexagonal 
w rench

Stop valve 

for LIQUID

Pressure gauge
(for R410A)

Precautions w hen us-

ing the control valve

When attaching the control valve 

to the service port, valve core may 

deform or loosen if excess pres-
sure is applied. This may  cause 

gas leak.

Service port

Charge hose 
(for R410A)

Body

Close

Open

Control valve

A

When attaching the control valve to 

the service port, make sure that the 

valve core is in closed position, and 

then tighten part A. Do not tighten 

part A or turn the body  hen valve 

core is in open position.

Union

Stop valve

Liquid 
pipe

Indoor 

unit

Stop valve  ith 

service port

Gas 
pipe

Refrigerant  gas            
cyl inder  

operating valve

(for R410A)

Gauge manifold 

valve (for R410A)

Charge hose 
(for R410A)

Refrigerant gas cyl inder for R410A w ith siphon

Electronic scale for refrigerant charging

Refrigerant (liquid)

Outdoor 

unit

Union

Union

Union

*   D unit is for 

4C36NA3 only.

Stop valve cap

(Torque 15  to 
22 ft-lb, 19.6 to 
29.4 N•m, 200 

to 300 kgf•cm)

Service port cap

(Torque 

10 to 13 ft-

lb, 

13.7 to 17.7 N•m, 

140 

to 180 kgf

•cm)

Stop valve 

for GAS

4-3. LOC ING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DR , HEAT)

COOL/DRY

HEAT

•  Description of the function:

  With this function, once the operation mode is locked to either COOL/DRY mode 

or HEAT mode, the air conditioner operates in that mode only.

*  Changing the setting is required to activate this function. Please explain about 

this function to your customers and ask them  hether they  ant to use it.

Ho  to loc  the operation mode

1) Be sure to turn off the main po er for the air conditioner before making the 

setting.

2) Set the “3” of SW1 on the outdoor controller board to ON to enable this function.

3) To lock the operation mode in COOL/DRY mode, set the “4” of SW1 on the 

outdoor controller board to OFF. To lock the operation in HEAT mode, set the 

same sw itch to ON.

4) Turn on the main pow er for the air conditioner.

SW1

ON

1   2   3   4   5   6

SW1

ON

1   2   3   4   5   6

L E D
SW1

SW8 7 1

SW2

4.  PURGING PROCEDURES, LEA  TEST, AND TEST RUN

 WARNING

W

h e n   o p e n i n g   o r  c l o s i n g   t h e   v a l v e  

b e l o w   fre e zi n g   t e m p e ra t u re s ,  
re fri g e ra n t   m a y   s p u rt   o u t   fro m   t h e  
g a p   b e t w e e n   t h e   v a l v e   s t e m   a n d   t h e  
v a l v e   b o d y ,   re s u l t i n g   i n   i n j u ri e s .

Cap

Valve stem

Valve body

Valve stem

WG79A858H01_01En.indd   6

2021/07/29   16:05:55

Summary of Contents for MXZ-3C30NA3

Page 1: ...inée à l INSTALLATEUR Cette notice ne décrit que l installation de l appareil extérieur Lors de l installation de l appareil intérieur consultez la notice d installation de cet appareil Toute altération structurelle requise pour l installation doit être conforme aux exi gences du code du bâtiment local M a n u a l d e i n s t a l a c i ó n Para el INSTALADOR En este manual só lo se describe la ins...

Page 2: ...o r i n s t a l l a t i o n The pressure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and incomplete installation could cause the pipes to burst or injury W h e n p u m p i n g d o w n t h e re fri g e ra n t s t o p t h e c o m p re s s o r b e fo re d i s c o n n e c t i n g t h e re fri g e ra n t p i p e s If the refrigerant pipes are disconnected w hile the com...

Page 3: ...F ro n t b l o w i n g s i d e o p e n As long as space indicated in the figure is provided it is allo ed to install the unit w here obstacles are behind and on the sides of the unit No obstacle above the unit FREE SPACE RE UIRED AROUND OUTDOOR UNIT Service space When installing the unit in an area that is enclosed w ith w alls such as a verandah be sure to have enough space as sho n belo In this ...

Page 4: ...sleeve 1 L Soft PVC hose 19 32 in 15 mm inner diameter or hard PVC pipe VP16 for drain socket 1 1 N o t e Place indoor outdoor unit connecting ire B and po er supply cord A at least 3 ft 1 m a ay from the TV antenna ire The ty for B to in the above table is quantity to be used per indoor unit More than 3 15 16 in 100 mm Open as a rule More than 19 11 16 in 5 00 mm if the front and both sides are o...

Page 5: ...ING IRES AND CONNECTING GROUND IRE Use solid conductor Min AWG14 or stranded conductor Min AWG14 Use double insulated copper ire ith 600 V insulation Use copper conductors only F o l l o w l o c a l e l e c t ri c a l c o d e PO ER SUPPL CABLE AND GROUND IRE Use solid or stranded conductor Min AWG12 Use copper conductors only F o l l o w l o c a l e l e c t ri c a l c o d e ARNING U s e t h e i n ...

Page 6: ...ected pipe size differs depending the models and the capacities of indoor units Indoor unit capacity 06 09 12 15 18 24 Indoor unit M series Liquid pipe size ø6 35 ø6 35 ø6 35 ø9 5 2 1 Gas pipe size ø9 5 2 ø9 5 2 ø12 7 ø15 88 Indoor unit S series Liquid pipe size ø6 35 ø6 35 ø6 35 ø9 5 2 Gas pipe size ø9 5 2 ø9 5 2 ø12 7 ø15 88 Indoor unit P series 2 Liquid pipe size ø6 35 ø6 35 ø6 35 ø9 5 2 Gas pi...

Page 7: ...R410A Compound pressure gauge for R410A 14 7 psi 0 101MPa Handle Low Handle High Vacuum pump for R410A Charge hose for R410A Close Open Hexagonal w rench Stop valve for LIQUID Pressure gauge for R410A Precautions w hen us ing the control valve When attaching the control valve to the service port valve core may deform or loosen if excess pres sure is applied This may cause gas leak Service port Cha...

Page 8: ...operation is done hile the po er is supplied Make sure not to contact parts other than the s itch including the P C board This may cause electric shock or burn by hot parts and live parts around the s itch Contacting the live parts may cause P C board damage To prevent electronic control P C board damage make sure to perform static elimination before operating this function This function does not ...

Page 9: ...n t p e n d a n t l i n s t a l l a t i o n a é re z l a p i è c e Tout contact entre le réfrigérant et une flamme pourrait provoquer l émission de gaz toxiques Des fuites de réfrigérant peuvent provoquer une asphyxie Aérez la pièce A la fin de l installation aucune fuite de réfrigérant ne doit être présente sur le circuit En cas de fuite de réfrigérant dans une pièce et si le réfrigérant entre en...

Page 10: ...ure extérieure est basse veillez à observer les instructions ci dessous N installez jamais l unité externe dans un endroit où le côté présentant l entrée la sortie d air risque d être directement exposé au vent Pour protéger l unité externe du vent installez la de façon à ce que l entrée d air soit face au mur Pour éviter toute exposition au vent il est recommandé d installer un écran de protectio...

Page 11: ...contenant des métaux de l étain p ex ou un treillis métallique utiliser un morceau de bois traité d une épais seur de 25 32 po 20 mm minimum entre le mur et la tuyauterie ou isoler la tuyauterie en lui appliquant 7 à 8 couches de ruban isolant en vinyle Pour utiliser la tuyauterie existante effectuer un cycle COOL REFROI DISSEMENT de 30 minutes et lancer l aspiration avant de procéder à la dépose ...

Page 12: ...liser un conducteur massif ou toronné min AWG12 Utiliser des conducteurs en cuivre uniquement R e s p e c t e r l e c o d e é l e c t ri q u e l o c a l A V E R T I S S E M E N T U t i l i s e r l e c â b l e d e c o n n e x i o n c o n fo rm e a u x n o rm e s t e c h n i q u e s p o u r raccorder les unités interne et externe et fixer le câble fermement sur la bloc de sortie de façon que le côté...

Page 13: ...sur les raccords de tuyauterie de l appareil extérieur N appliquez pas d huile réfrigérante sur les filetages Un couple de serrage excessif endommagera la vis 2 Pour effectuer le raccordement alignez d abord le centre puis serrez à la main l écrou à évasement de 3 à 4 tours 3 Serrez l écrou évasé avec une clé dynamométrique comme indiqué dans le tableau Un serrage excessif pourrait endommager l éc...

Page 14: ...A I D E F O N C T I O N N E M E N T 1 Retirez le bouchon de l ouverture de service du robinet d arrêt du côté du conduit de gaz de l unité externe A l origine les robinets d arrêt sont com plètement fermés et recouverts d un capuchon 2 Raccordez la vanne du collecteur à jauge et la pompe à vide à l ouverture de service du robinet d arrêt du côté du conduit de gaz de l unité externe 3 Mettez la pom...

Page 15: ... n t l e m é c a n i s m e d e p ro t e c t i o n c o n t re u n e re m i s e e n m a rc h e t ro p ra p i d e Lorsque le compresseur s arrête le dispositif de protection contre la remise en marche à trop brève échéance s enclenche Le compresseur restera arrêté trois minutes avant de se remettre en marche afin de protéger le climatiseur F o n c t i o n d e c o rre c t i o n d e c â b l a g e t u y...

Page 16: ... sistema o averí as en la unidad En el peor de los casos esto podr a llegar a ser un serio impedimento para garantizar el uso seguro del producto N o d e s c a rg u e e l re fri g e ra n t e e n e l a m b i e n t e S i s e p ro d u c e n fu g a s d e re fri g e ra n t e d u ra n t e l a i n s t a l a c i ó n v e n t i l e l a h a b i t a c i ó n Si el refrigerante entra en contacto con una llama p...

Page 17: ... sea baja observe las instrucciones siguientes No instale nunca la unidad exterior en un lugar en el que el lado de entra da salida de aire quede expuesto directamente al viento Para evitar la exposició n al viento instale la unidad exterior con el lado de entrada de aire hacia la pared Para evitar la exposició n al viento se recomienda instalar una placa de flectora en el lado de salida de aire d...

Page 18: ... y ambos lados está n abiertos Después de la prueba de fugas aplique material aislante de modo que no queden huecos Cuando los tubos deban instalarse en una pared con contenido metá lico placas de lat n o rejillas met licas ponga un trozo de madera tratada qu micamente de 25 32 pulg 20 mm o m s de grosor entre la pared y los tubos o envuelva los tubos con 7 u 8 vueltas de cinta aislante de vinilo ...

Page 19: ... R A Utilice un conductor s lido o trenzado con un calibre m n AWG12 Use nicamente conductores de cobre S i g a l a n o rm a t i v a e l é c t ri c a l o c a l A T E N C I Ó N C o n e c t e l a s u n i d a d e s i n t e ri o r y e x t e ri o r c o n e l c a b l e d e c o n e x i ó n normalizado destinado a este fin y su ete bien el cable al panel de t e rm i n a l e s d e m o d o q u e n o q u e d...

Page 20: ...e tuber as E a partir de la entrada de la unidad exterior Sujete con cinta adhesiva el extremo de la cinta de tuberí as E Cuando las tuberí as deban colocarse por encima del techo en un armario empotrado o en lugares con una temperatura y humedad elevadas tendr que aplicar una cantidad suplementaria de aislante para evitar la conden sació n 1 Corte el tubo de cobre correctamente con un cortador de...

Page 21: ...terarse en el sistema y afectar a la operaci n normal del acondicionador del aire Recuerde también cargar el refrigerante lí quido poco a poco ya que de lo contrario puede bloquear el compresor Para mantener alta la presi n del cilindro de gas caliente el cilindro de gas con agua caliente a menos de 104 F 40 C en las estaciones fr as Nunca utilice fuego o vapor Unió n Vá lvula de retenció n Tuberí...

Page 22: ...rtas N o t a Durante la detecció n el funcionamiento de la unidad interior estará controlado por la unidad exterior Durante la detecció n la unidad interior dejará de funcionar au tomá ticamente Esto no es un fallo de funcionamiento Procedimiento Mantenga presionado el interruptor de correcci n de tuber as conexiones SW871 1 minuto o má s tras conectar la alimentació n La correcci n tarda entre 10...

Page 23: ...A4_white_tombo indd 1 2018 08 09 14 11 29 ...

Page 24: ...HEAD OFFICE TOKY O BLDG 2 7 3 MARUNOUCHI CHIY ODA KU TOKY O 100 8 3 10 JAPAN WG7 9A8 5 8 H01 WG79A858H01_cover4 indd 2 2021 02 10 8 44 04 ...

Reviews: