En-5

4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)

4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT

•  Description of the function:

  With this function, once the operation mode is locked to either COOL/DRY mode 

or HEAT mode, the air conditioner operates in that mode only.

*  Changing the setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use it.

[How to lock the operation mode]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Set the “2” of SW1 on the outdoor controller board to ON to enable this function.

3) To lock the operation mode in COOL/DRY mode, set the “1” of SW1 on the 

outdoor controller board to OFF. To lock the operation in HEAT mode, set the 

same switch to ON.

4) Turn on the main power for the air conditioner.

•  Description of the function:

  With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. 

However, please note that the cooling and heating capacity may lower if this function is activated.

*  Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.

Lower the operating noise

[How to lower the operating noise]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Set the “3” of SW1 on the outdoor controller board to ON to enable this function.

3) Turn on the main power for the air conditioner.

4-5. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate 

properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

Make sure that the following is done.

•  Power is supplied to the unit.

•  Stop valves are open.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

5-1. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.

1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.

3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa 

[Gauge] (0 kgf/cm

2

).

4) Start the emergency COOL operation on all the indoor units.

  To start the emergency operation in COOL mode, disconnect the power supply plug and/or turn off the breaker. After 15 seconds, connect the power supply 

plug and/or turn on the breaker, and then press the E.O. SW once. (The emergency COOL operation can be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

).

6) Stop the emergency COOL operation.

  Press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details .

When pumping down the refrigerant, stop the compressor before disconnecting 

the refrigerant pipes. The compressor may burst if air etc. get into it.

 

WARNING

4-6. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, 

how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

COOL/DRY

HEAT

5.  RELOCATION AND MAINTENANCE

JG79A379H03_en.indd   5

2016/03/02   9:49:08

Summary of Contents for MXZ-2C30VA

Page 1: ...relativo manuale di instal lazione Εγχειρίδιο εγκατάστασης Για τον ΤΕΧΝΙΚΟ Στο παρόν εγχειρίδιο περιγράφεται μόνο η εγκατάσταση της μονάδας εξωτερικού χώρου Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalaçã...

Page 2: ...installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and incomplete installation could cause the pipes to burst or injury ...

Page 3: ...baffle board on the air outlet side of the outdoor unit Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring Where there is high frequency or wireless equipment Where there is emission of high levels of VOCs incl...

Page 4: ...onnecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 2 PIPE CONNEC TION is completed After making connections between both power supply cord A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Indoor outdoor unit connecting wire OUTDOOR UNIT 35 mm 15 mm Lead wire Terminal block UNIT UNIT Term...

Page 5: ... cap of service port to obtain the initial status 10 Leak test WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely Stop valve for GAS Stop valve cap Torque 19 6 to 29 4 N m 200 to 300 kgf cm Gauge manifold valve for R410A Compound pressure gauge for R41...

Page 6: ...nnecting wires cannot be detected Thus be sure to perform the test run one by one Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner 5 1 PUMPING DOWN When relocating or disposing ...

Page 7: ...инить при работающем компрессоре и откры том стопорном клапане возможно засасывание воздуха и чрезмерное повыше ние давления в контуре охлаждения Это может привести к разрыву труб или нанесению увечий n При установке прибора надежно подсоедините трубы с хладагентом до запуска компрессора Если компрессор запускается до подсоединения труб с хладагентом и при от крытом стопорном клапане возможно заса...

Page 8: ...ентой 7 8 раз Для использования имеющегося трубопровода выполните опе рацию COOL ОХЛАЖДЕНИЕ в течение 30 минут и осуществите откачку перед демонтажем старо го кондиционера Повторно смон тируйте раструб в соответствии с размером для нового количества хладагента Воздухозаборное отверстие Примечание При эксплуатации кондиционера при низкой температуре наружно го воздуха обязательно следуйте приведенн...

Page 9: ...да со единения внутреннего наружного приборов В убедитесь что и провод и шнур закреплены с помощью проводных зажимов Клеммная колодка для электропитания Сервисная панель 35 мм 15 мм Провод соединения внутреннего наружного приборов НАРУЖНЫЙ ПРИБОР ЭЛЕКТРОПИТАНИЕ N 230 В 50 Гц Силовой провод ПРИБОР Клеммная колодка для электропитания Обязательно присоедините каждый винт к соответствующей клемме при ...

Page 10: ...ном случае состав хладагента в системе может измениться что отрицательно повлияет на производительность кондиционера 9 Затяните колпачок сервисного порта для возврата к исходному состоянию 10 Проверка на отсутствие утечек 4 1 ПРОЦЕДУРЫ ПРОДУВКИ И ПРОВЕРКА НА ОТСУТСТВИЕ УТЕЧЕК Если некоторые порты не исполь зуются убедитесь что их гайки надежно затянуты Стопорный клапан для ГАЗА Колпачок стопор ног...

Page 11: ... следует выполнять поэтапно Убедитесь что выполнено следующее На прибор подается питание Запорные клапаны открыты О защитном механизме повторного запуска После остановки компрессора включается защитное устройство повторного запуска отключающее компрессор на несколько минут для защиты кондиционера 4 6 ПОЯСНЕНИЕ ДЛЯ ПОЛЬЗОВАТЕЛЯ Используя ИНСТРУКЦИИ ПО ЭКСПЛУАТАЦИИ объясните пользователю как эксплуа...

Page 12: ...HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JG79A379H03 ...

Reviews: