4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)

4-2. GAS CHARGE

Perform gas charge to unit.

1) Connect gas cylinder to the service port of stop valve.

2) Perform  air  purge  of  the  pipe  (or  hose)  coming  from  refrigerant  gas 

cylinder.

3) Replenish specified amount of the refrigerant, while operating the air 

conditioner for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the 

refrigerating cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure 

to use liquid refrigerant. Adding gas refrigerant may change the composi

-

tion of the refrigerant in the system and affect normal operation of the air 

conditioner. Also, charge the system slowly, otherwise the compressor 

will be locked.

To maintain the high pressure of the gas cylinder, warm the gas cylinder 

with warm water (under 40°C) during cold season. But never use naked 

fire or steam.

Refrigerant gas            

cylinder 

 

operating valve

(for R410A)

Indoor 

unit

Charge hose (for R410A)

Refrigerant gas cylinder 

for R410A with siphon

Electronic scale for 

refrigerant charging

Refrigerant (liquid)

4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT

•  Description of the function:

  With  this  function,  you  can  lower  the  operating  noise  of  the  outdoor 

unit when the operation load is small, for example, during nighttime in 

COOL mode. However, please note that the cooling capacity can also 

be lowered if this function is activated.

*  Initial setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use 

it.

[How to lower the operating noise]

1) Be sure to turn off the main power for the air conditioner before mak-

ing the setting.

2) Set the 3rd Dip Switch of SW1 on the outdoor controller board to ON 

to enable this function.

3) Turn on the main power for the air conditioner.

•  Description of the function:

  With  this  function,  you  can  lock  the  operation  mode  of  the  outdoor 

unit. Once the operation mode is locked to either COOL/DRY mode or 

HEAT mode, the air conditioner operates in that mode only.

*  Initial setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use 

it.

[How to lock the operation mode]

1) Be sure to turn off the main power for the air conditioner before mak-

ing the setting.

2) Set the 2nd Dip Switch of SW1 on the outdoor controller board to ON 

to enable this function.

3) To  lock  the  operation  mode  in  COOL/DRY  mode,  set  the  1st  Dip 

Switch of SW1 on the outdoor controller board to OFF. To lock the op-

eration in HEAT mode, set the same switch to ON.

4) Turn on the main power for the air conditioner.

Indoor 

unit

Union

Union

Liquid pipe

Gas pipe

Liquid pipe

Gas pipe

Stop valve

Service port

Outdoor 

unit

Gauge manifold 

valve (for R410A)

Lower the operating 

noise

SW1

Operation mode

COOL

DRY

HEAT

MXZ-2BVA-A1 JG79A299H01.indd   6

2009/10/13   10:32:19

Summary of Contents for MXZ-2B52VA

Page 1: ...ON AND MAINTENANCE 7 Split type Air Conditioner MXZ 2B52VA Refer to the installation manual of each indoor unit for indoor unit installation English IMPORTANT NOTES TO COMPLY WITH THE REQUIREMENTS OF AUSTRALIAN STANDARD AS NZS 3000 ELECTRICAL INSTALLATIONS Wiring Rules THE ELECTRICAL WIRING REQUIRED BETWEEN THE INDOOR AND OUTDOOR UNITS MUST BE INSTALLED BY A LICENCED ELECTRICAL CONTRACTOR ...

Page 2: ...t with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or materials and incomplete installation could cause the pipes to burst or injury n When pumping down the refrigerant stop the compressor before disconnecting the refr...

Page 3: ... prevent exposure to wind it is recommended to install a baffle board on the air outlet side of the outdoor unit Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring Where there is high frequency or wireless equi...

Page 4: ...s More than 35 mm For future servicing give extra length to the connecting wires Terminal block for power supply 1 Remove the service panel 2 Loosen terminal screw and connect indoor outdoor unit connecting wire B from the indoor unit correctly on the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external...

Page 5: ... R410A Precautions when using the control valve When attaching the control valve to the service port valve core may de form or loosen if excess pressure is applied This may cause gas leak Service port Charge hose for R410A Body Close Open Control valve A When attaching the control valve to the service port make sure that the valve core is in closed position and then tighten part A Do not tighten p...

Page 6: ... COOL mode However please note that the cooling capacity can also be lowered if this function is activated Initial setting is required to activate this function Please explain about this function to your customers and ask them whether they want to use it How to lower the operating noise 1 Be sure to turn off the main power for the air conditioner before mak ing the setting 2 Set the 3rd Dip Switch...

Page 7: ...llowing the procedure below so that no refrigerant is released into the atmos phere 1 Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the ...

Page 8: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JG79A299H01 ...

Reviews: