Mitsubishi Electric MXZ-2B52VA Installation Manual Download Page 4

4

1-7. DRAIN PIPING FOR OUTDOOR UNIT

Please perform the drain piping work only when draining from one place.

1) Provide drain piping before indoor and outdoor piping connection. 

2) Connect drain hose I.D.15 mm as shown in the illustration.

3) Make sure to provide drain piping with a downhill grade for easy drain flow.

Note:

Install the unit horizontally.

Do not use the drain socket in the cold regions. Drain may freeze and it makes the fan stop.

The outdoor unit produces condensate during the heating operation. Select the installation 

place to ensure to prevent the outdoor unit and/or the grounds from being wet by drain water 

or damaged by frozen drain water. 

2.  OUTDOOR UNIT INSTALLATION

2-1. CONNECTING  WIRES FOR OUTDOOR UNIT

Indoor/outdoor unit connecting wire

<OUTDOOR UNIT>

35 mm

15 mm

Lead wire

•  Be  sure  to  attach  each  screw  to  its  correspondent  terminal  when  

  securing the cord and/or the wire to the terminal block.

• Make earth wire a little longer than others. (More than 35 mm)

• For future servicing, give extra length to the connecting wires.

Terminal block  

for power supply

1) Remove the service panel.

2) Loosen  terminal  screw,  and  connect  indoor/outdoor  unit  connecting 

wire (B) from the indoor unit correctly on the terminal block. Be careful 

not to make mis-wiring. Fix the wire to the terminal block securely so 

that no part of its core is appeared, and no external force is conveyed 

to the connecting section of the terminal block. 

3) Firmly tighten the terminal screws to prevent them from loosening. Af

-

ter tightening, pull the wires lightly to confirm that they do not move.

4) Perform 2) and 3) for each indoor unit.

5) Connect power supply cord (A).

6) Fix indoor/outdoor unit connecting wire (B) and power supply cord (A) 

with the cable clamps.

7) Close the service panel securely. Make sure that 3-2. PIPE CONNEC

-

TION is completed.

•  After making connections between both power supply cord (A) and 

indoor/outdoor unit connecting wire (B), be sure to fix both cable and 

wire with cable clamps.

Terminal 

block

Terminal 

block

UNIT

UNIT

Terminal block for 

power supply

<INDOOR UNIT>

POWER SUPPLY

~/N 230 V 50 Hz

Drain socket

Drain hose

Service panel

MXZ-2BVA-A1 JG79A299H01.indd   4

2009/10/13   10:32:06

Summary of Contents for MXZ-2B52VA

Page 1: ...ON AND MAINTENANCE 7 Split type Air Conditioner MXZ 2B52VA Refer to the installation manual of each indoor unit for indoor unit installation English IMPORTANT NOTES TO COMPLY WITH THE REQUIREMENTS OF AUSTRALIAN STANDARD AS NZS 3000 ELECTRICAL INSTALLATIONS Wiring Rules THE ELECTRICAL WIRING REQUIRED BETWEEN THE INDOOR AND OUTDOOR UNITS MUST BE INSTALLED BY A LICENCED ELECTRICAL CONTRACTOR ...

Page 2: ...t with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or materials and incomplete installation could cause the pipes to burst or injury n When pumping down the refrigerant stop the compressor before disconnecting the refr...

Page 3: ... prevent exposure to wind it is recommended to install a baffle board on the air outlet side of the outdoor unit Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring Where there is high frequency or wireless equi...

Page 4: ...s More than 35 mm For future servicing give extra length to the connecting wires Terminal block for power supply 1 Remove the service panel 2 Loosen terminal screw and connect indoor outdoor unit connecting wire B from the indoor unit correctly on the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external...

Page 5: ... R410A Precautions when using the control valve When attaching the control valve to the service port valve core may de form or loosen if excess pressure is applied This may cause gas leak Service port Charge hose for R410A Body Close Open Control valve A When attaching the control valve to the service port make sure that the valve core is in closed position and then tighten part A Do not tighten p...

Page 6: ... COOL mode However please note that the cooling capacity can also be lowered if this function is activated Initial setting is required to activate this function Please explain about this function to your customers and ask them whether they want to use it How to lower the operating noise 1 Be sure to turn off the main power for the air conditioner before mak ing the setting 2 Set the 3rd Dip Switch...

Page 7: ...llowing the procedure below so that no refrigerant is released into the atmos phere 1 Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the ...

Page 8: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JG79A299H01 ...

Reviews: