30
Check of compressor winding
Check of compressor operation time
●
Disconnect the connector (CN61) between the compressor and
intelligent power module, and measure the resistance between the
compressor terminals.
<<Measurement point>>
at 3 points
BLK-WHT
BLK-RED
WHT-RED
<<Judgement>>
Refer to 11-4.
0[
"
] ···············Abnormal [short]
Infinite[
"
] ·······Abnormal [open]
NOTE: 1. Be sure to zero the ohmmeter before measurement.
w
Measure the resistance between the
lead wires at 3 points.
●
Connect the compressor and activate the inverter. Then measure the
time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit.
(Test run operation : Refer to 8-3.)
<<Measurement>>
Measure the time from the start of compressor to the stop of compressor
due to over current.
0 second
10 seconds
10 minutes
1 second
2 seconds
Normal
Abnormal
(Refrigerant circuit defect)
(closed valve)
Abnormal
(Poor contact,)
(Outdoor P.C.board defect)
(disconnected connector)
Abnormal
(Compressor lock out)
(Starting defect)
Abnormal
(IPM failure)
(Compressor winding short)
Compressor starts
<<Judgement>>
For reference
D
E
Check of compressor start failure
F
Yes
No
Yes
Confirm that
1
~
4
is normal.
•Electrical circuit check
1
Contact of the compressor connector (including CN61)
2
Output voltage of inverter P.C.board and balance of them (See 11-5.
B
)
3
Direct current voltage between DB61(+) and (-) on inverter P.C.board
4
Voltage between outdoor terminal block S1-S2
Check the refrigerant circuit.
Check the stop valve.
w
1
Heat the compressor with
a drier for about 20 minutes.
Do not recover refrigerant
gas while heating.
Compressor start failure. Activate pre-heat control.
(Refer to 10-2. "PRE-HEAT CONTROL SETTING")
After the compressor is heated with a drier,
does the compressor start?
w
1
Does the compressor run for 10 seconds
or more after it starts?
No
Replace the compressor
Heating part
OBH489--1.qxp 07.8.9 11:53 AM Page 30
Summary of Contents for MUZ-FD25VA
Page 2: ...2 ...
Page 8: ...8 6 WIRING DIAGRAM MUZ FD25VA MUZ FD35VA ...
Page 9: ...9 MUZ FD25VAH MUZ FD35VAH ...
Page 42: ...42 ...
Page 43: ...43 ...