4
Outdoor model
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at20
:
)
Model
Winding
resistance(at20
:
)
Dimensions W
O
H
O
D
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity(R22)
Refrigerating oil (Model)
kW
R
/h
K
/h
A
A
W
A(kW)
%
A
A
A
W
"
"
mm
kg
dB
rpm
kg
cc
Opetate 1 unit
A
2.5
1.1
3.43
775
98.2
3.10
0.33
3.09
Opetate 1 unit
B or C
2.7
1.2
4.23
965
99.2
3.90
0.33
2.70
Opetate 2 unit
A+B or A+C
2.4+2.7
0.9+1.2
7.56
1,740
99.9
6.99
0.57
2.82
Opetate 3 unit
A+B+C
2.4+1.75
✕
2
0.9+0.3
✕
2
7.79
1,785
99.6
7.22
0.57
3.12
MUX-20TV -
E1
Single phase
230V, 50Hz
Opetate 2 unit
B+C
1.75
✕
2
0.3
✕
2
High: 2,460 / Low: 1,920
15
4.36
1,000
—
99.7
40
4.03
0.33
3.27
RH140VHAT (Room A) / RH174VHAT (Room B,C)
700/800
C-R 4.03/3.30
C-S 5.71/5.80
RA6V60-DA
WHT-BLK 90 BLK-YLW 54
BLK-RED 146
840
✕
640
✕
330
62
52
High: 730 / Low: 580
2
Room A : 0.8
Room B,C : 0.96
300(MS56) / 300(MS56)
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance(C.O.P)
Outdoor unit power supply
Indoor unit No.
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor
DB27°C / WB19°C
Outdoor
DB35°C / WB(24°C)
OB284-1.qxp 01.4.26 8:59 PM Page 4