51
Check of outdoor thermistor
Measure
resistance
between CN 661
1
and
2
.
Measure
resistance
between CN 662
3
and
4
.
No
Yes
Replace the
thermistor.
Reconnect CN661
and CN662.
Turn ON the power
supply and press
the EMERGENCY
OPERATION
switch.
Does the resistance
of thermistor have
the characteristics
on page 45?
No
Yes
Does the unit operate
10 minutes or more?
Replace the deicer P.C.
board.
Ok
W
1.
W
1. It is thought defective contact of the connector.
Turn OFF the
power supply.
Ambient temperature
thermistor(RT63)
Defrost thermistor(RT61)
w
Disconnect the connectors CN661 and/or CN662 from the deicer P.C. board.
(Check the characteristics of each thermistor.)
H
When OPERATION INDICATOR lamp flashes 6-time.
Thermistors in the outdoor unit are abnormal.
OB267--2.qxp 01.12.19 3:00 PM Page 51