FRONT GRILLE REMOVAL
• Remove front grille and transportation support.
4-1-(5)
OPENING KNOCKOUT HOLE
• Remove knockout holes with hammering it.
4-1-(6)
FIXING UNIT TO INSTALLATION PLATES
1. Suspending unit from installation plates.
• Hoist unit so that hanging bolt (4) on the sides of unit fit into holes in installation plates
1
.
2. Securing unit to installation plates.
• Be sure to tighten unit fixing screw
2
to unit securely.
FRONT
Remove 3 screws
Transportation support
* After installing com-
pletely, please remove
this part because this is
used for transportation
only.
Front grille
Knockout hole
Knockout hole for drain pipe
Unit fixing screw
2
Unit fixing screw
2
Hanging bolt
• Be sure to set hanging bolt
in this position to keep
unit’s inclination.
4-1-(2)
FIXING OF INSTALLATION PLATES
1. Set installation plates to installation plate fixing bolts.
• Set installation plates
1
to installation plate fixing bolts
J
so that the distance between insides of installation plates
is adjusted to length as shown in the right.
1
Installation plate
• Installation plates
1
should be fixed on one way direction,
as shown in Fig. 1.
Don’t fix as shown in Fig. 2.
• Be sure to confirm letters “FRONT” in installation plates
1
,
set “FRONT” side to air outlet side of indoor unit.
a
“FRONT”
1
Installation plate
2. In case of fixing installation plates
1
above the ceiling, put
installation plates fixing bolt through a nut, a spring washer,
the installation plate, a spring washer, and double nut. (Fig. 3)
In case of fixing installation plates
1
forward the ceiling
directly, also put installation plate fixing bolt through the in-
stallation plate, a spring washer, and double nuts. (Fig. 4)
a
Ceiling
K
-1
Nut (M10)
1
Installation plate
K
-2
Spring washer
J
Installation plate fixing bolt
K
-3
Double nut (M10)
3. Check that the four corners are horizontal with level gauge.
(Fig. 5)
a
Level gauge
4-1-(3)
DRILLING HOLE
Determine the locations of holes for refrigerant pipe
A
and drain
pipe
D
.
• Use the installation pattern as mentioned in 4-1-(1).
• Be sure to confirm the dimensions as shown in the right.
a
Horizontal base line
b
Hole for refrigerant pipe
c
Hole for drain pipe
1
Installation plate
• Specially, drill the hole for drain pipe with designate dimen-
sion to keep an inclination.
d
Horizontal base line
e
Hanging bolt
f
Wall
1
1028 mm
1
a
J
a
K
-1
K
-2
1
K
-2
K
-3
1
K
-2
K
-3
J
a
(Fig. 1)
(Fig. 2)
(Fig. 3)
(Fig. 4)
a
1
b
c
0
115
188
132
124
0
Ø
40
Ø75
a
(Fig. 5)
(unit : mm)
(unit : mm)
e
f
d
188
193
199
204
115
155
0
100
200
300
FRONT