background image

5-1. REMOVING AND INSTALLING THE PANEL ASSEMBLY

5-3. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the 
procedure below so that no refrigerant is released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe 

side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it 

can be easily closed fully when the pressure gauge shows 0 MPa [Gauge] (0 kgf/cm

2

).

4) Start the emergency COOL operation.
 

To start the emergency operation in COOL mode, disconnect the power supply plug and/
or turn off the breaker. After 15 seconds, connect the power supply plug and/or turn on 
the breaker, and then press the E.O. SW once. (The emergency COOL operation can be 
performed continuously for up to 30 minutes.)

5)  Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge 

shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

).

6) Stop the emergency COOL operation.
  Press the E.O. SW several times until all LED lamps turn off. Refer to operating instruc-

tions for details.

5. RELOCATION 

AND 

MAINTENANCE

When pumping down the refrigerant, stop the compressor before disconnecting the 
refrigerant pipes. The compressor may burst if air etc. get into it.

 

WARNING

5-2. REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the installation 
plate.
When releasing the corner part, release both left and right 
bottom corner part of indoor unit and pull it downward and 

IRUZDUGDVVKRZQLQWKH¿JXUHRQWKHULJKW

If the above method cannot be used

Remove the panel. Then, insert hexagonal wrenches into the square holes on the left 

DQGULJKWVLGHVRIWKHXQLWDQGSXVKWKHPXSDVVKRZQLQWKHIROORZLQJ¿JXUH7KHERW

-

tom of the indoor unit lowers and releases the hooks.

Removal procedure

5HPRYHWKHVFUHZVZKLFK¿[WKHSDQHODVVHPEO\

2) Remove the panel assembly. Be sure to remove its 

ERWWRPHQG¿UVW

Installation procedure

1) Install the panel assembly following the removal 

procedure in reverse. 

2) Be sure to press the positions as indicated by the 

arrows in order to attach the assembly completely 
to the unit.

Push

Lower

Square hole

Summary of Contents for MSZ-GL71VGD

Page 1: ...that there is no dust clogging or loose parts in both the outlet and the plug Make sure that the power supply plug is pushed completely into the outlet If there is dust clogging or loose parts on the power supply plug or the outlet it could cause electric shock or UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ replace it Attach the electrical cover to the indoor unit and the service panel to t...

Page 2: ...maldehyde etc which may cause chemical cracking 7KH DSSOLDQFH VKDOO EH VWRUHG VR DV WR SUHYHQW PHFKDQLFDO GDPDJH IURP RFFXUULQJ Pipe length and height difference Max pipe length 30 m Max height difference 15 m Max number of bends 6 7 10 Refrigerant adjustment A 8 20 g m Insulation thickness 9 10 8 mm INDOOR UNIT WARNING Install the indoor unit in rooms which exceed 3 1 m2 KHUH DLUÀRZ LV QRW EORFNH...

Page 3: ...to local code requirements To comply with the requirements of Australian standard AS NZS 3000 electrical installations wiring rules the electrical wiring required between the indoor and outdoor units must be installed by a licenced electrical contractor Check that cabling will not be subject to wear corrosion excessive pres sure vibration sharp edges or any other adverse environmental effects The ...

Page 4: ...the front panel 1 Open the front panel 2 Remove VA clamp 3 Pass indoor outdoor unit connecting wire A from the back of the indoor unit and process the end of the wire RRVHQ WHUPLQDO VFUHZ DQG FRQQHFW UVW WKH HDUWK ZLUH WKHQ LQGRRU RXWGRRU XQLW FRQ necting wire A to the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appear...

Page 5: ...and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening After tightening SXOO WKH ZLUHV OLJKWO WR FRQ UP WKDW WKH GR QRW PRYH 4 Connect power supply cord K 5 Fix indoor outdoor unit connecting wire A and power supply cord K with the cord clamp 6 Close the service panel securely 0DNH HDUWK ZLUH D OLWWOH OR...

Page 6: ...ompound pressure gauge for R32 R410A 0 101 MPa 760 mmHg Handle Low Handle High Adapter for preventing the EDFN ÀRZ Charge hose for R32 R410A Close Open Hexagonal wrench Precautions when using the control valve When attaching the control valve to the service port valve core may deform or loosen if excess pressure is applied This may cause gas leak Service port Body Close R32 Open Control valve A Wh...

Page 7: ...MPa Gauge approx 0 5 to 0 kgf cm2 6 Stop the emergency COOL operation Press the E O SW several times until all LED lamps turn off Refer to operating instruc tions for details 5 RELOCATION AND MAINTENANCE When pumping down the refrigerant stop the compressor before disconnecting the refrigerant pipes The compressor may burst if air etc get into it WARNING 5 2 REMOVING THE INDOOR UNIT Remove the bot...

Page 8: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: