JG79B530H01

Required Tools for Installation

Phillips screwdriver
Level
Scale
Utility knife or scissors
75 mm hole saw
Torque wrench
Wrench (or spanner)

4 mm hexagonal wrench
Flare tool for R32, R410A
Gauge manifold for R32, R410A
Vacuum pump for R32, R410A
Charge hose for R32, R410A
Pipe cutter with reamer

SPLIT-TYPE AIR CONDITIONERS

INSTALLATION MANUAL

ENGLISH

Model names are indicated in 1-3.

REFRIGERANT

Appropriate personal protective equipment

The installer should ensure they check the respective Work Health 
and Safety (WHS) Act within their jurisdiction as the requirements 
and obligations may differ.

1. BEFORE 

INSTALLATION

WARNING

7KLVXQLWXVHVDÀDPPDEOHUHIULJHUDQW
,IUHIULJHUDQWOHDNVDQGFRPHVLQFRQWDFWZLWK¿UHRUKHDWLQJSDUWLWZLOOFUHDWHKDUPIXOJDVDQGWKHUHLVULVNRI¿UH

Read the OPERATING INSTRUCTIONS carefully before operation.

Service personnel are required to carefully read the OPERATING INSTRUCTIONS and INSTALLATION MANUAL before operation.

Further information is available in the OPERATING INSTRUCTIONS, INSTALLATION MANUAL, and the like.

1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY

‡ %HVXUHWRUHDG³7+()2//2:,1*6+28/'$/:$<6%(2%6(59(')256$)(7<´EHIRUHLQVWDOOLQJWKHDLUFRQGLWLRQHU
‡ %HVXUHWRREVHUYHWKHZDUQLQJVDQGFDXWLRQVVSHFL¿HGKHUHDVWKH\LQFOXGHLPSRUWDQWLWHPVUHODWHGWRVDIHW\
‡ $IWHUUHDGLQJWKLVPDQXDOEHVXUHWRNHHSLWWRJHWKHUZLWKWKH23(5$7,1*,16758&7,216IRUIXWXUHUHIHUHQFH
‡ :KHQXVLQJWKLVSURGXFWLQ$XVWUDOLDFDUHIXOO\UHDGWKH$XVWUDOLDQ,QVWLWXWHRI5HIULJHUDWLRQDQG)ODPPDEOHUHIULJHUDQWV6DIHW\*XLGHLQ$LUFRQGLWLRHDWLQJ$,5$+DVZHOO

 

CAUTION

(Could lead to serious injury in particular environments when operated incorrectly.)

 

WARNING

(Could lead to death, serious injury, etc.)

  Do not install the unit by yourself (user).

 ,QFRPSOHWH LQVWDOODWLRQ FRXOG FDXVH ¿UH HOHFWULF VKRFN

injury due to the unit falling, or leakage of water. Consult 

WKHGHDOHUIURPZKRP\RXSXUFKDVHGWKHXQLWRUDTXDOL¿HG

installer.

 Perform the installation securely referring to the 

installation manual.

 ,QFRPSOHWH LQVWDOODWLRQ FRXOG FDXVH ¿UH HOHFWULF VKRFN

injury due to the unit falling, or leakage of water. 

  When installing the unit, use appropriate protective 

equipment and tools for safety.

 

Failure to do so could cause injury.

  Install the unit securely in a place which can bear the 

weight of the unit.

  If the installation location cannot bear the weight of the 

unit, the unit could fall causing injury.

■ 

(OHFWULFDOZRUNVKRXOGEHSHUIRUPHGE\DTXDOL¿HG

experienced electrician, according to the installation 
manual. Be sure to use an exclusive circuit. Do not 
connect other electrical appliances to the circuit.

 ,IWKHFDSDFLW\RIWKHSRZHUFLUFXLWLVLQVXI¿FLHQWRUWKHUH

LVLQFRPSOHWHHOHFWULFDOZRUNLWFRXOGUHVXOWLQD¿UHRUDQ

electric shock.

  Earth the unit correctly.

 

Do not connect the earth to a gas pipe, water pipe, light-
ning rod, or telephone earth. Defective earthing could 
cause electric shock.

■ 

Do not damage the wires by applying excessive pres-
sure with parts or screws.

 'DPDJHGZLUHVFRXOGFDXVH¿UHRUHOHFWULFVKRFN

■ 

Be sure to cut off the main power in case of setting 
up the indoor P.C. board or wiring works.

 

Failure to do so could cause electric shock.

 8VH WKH VSHFL¿HG ZLUHV WR FRQQHFW WKH LQGRRU DQG

RXWGRRUXQLWVVHFXUHO\DQGDWWDFKWKHZLUHV¿UPO\WR

the terminal block connecting sections so the stress 
of the wires is not applied to the sections. Do not 
extend the wires, or use intermediate connection.

 ,QFRPSOHWHFRQQHFWLQJDQGVHFXULQJFRXOGFDXVH¿UH

■ 

'RQRWLQVWDOOWKHXQLWLQDSODFHZKHUHLQÀDPPDEOH

gas may leak.

 

If gas leaks and accumulates in the area around the unit, 
it could cause an explosion.

 Do not use intermediate connection of the power 

cord or the extension cord and do not connect many 
devices to one AC outlet.

 ,WFRXOGFDXVHD¿UHRUDQHOHFWULFVKRFNGXHWRGHIHFWLYH

contact, defective insulation, exceeding the permissible 
current, etc.

■ 

%HVXUHWRXVHWKHSDUWVSURYLGHGRUVSHFL¿HGSDUWV

for the installation work.

 

The use of defective parts could cause an injury or leakage 

RIZDWHUGXHWRD¿UHDQHOHFWULFVKRFNWKHXQLWIDOOLQJ

etc.

■ 

When plugging the power supply plug into the outlet, 
make sure that there is no dust, clogging, or loose 
parts in both the outlet and the plug. Make sure that 
the power supply plug is pushed completely into the 
outlet.

  If there is dust, clogging, or loose parts on the power 

supply plug or the outlet, it could cause electric shock or 

¿UH,IORRVHSDUWVDUHIRXQGRQWKHSRZHUVXSSO\SOXJ

replace it.

■ 

Attach the electrical cover to the indoor unit and the 
service panel to the outdoor unit securely.

 

If the electrical cover of the indoor unit and/or the service 
panel of the outdoor unit are not attached securely, it could 

UHVXOWLQD¿UHRUDQHOHFWULFVKRFNGXHWRGXVWZDWHUHWF

■ 

When installing, relocating, or servicing the unit, 

PDNHVXUHWKDWQRVXEVWDQFHRWKHUWKDQWKHVSHFL¿HG

refrigerant (R32) enters the refrigerant circuit.

 

Any presence of foreign substance such as air can cause 
abnormal pressure rise and may result in explosion or 
injury. The use of any refrigerant other than that speci-

¿HGIRUWKHV\VWHPZLOOFDXVHPHFKDQLFDOIDLOXUHV\VWHP

malfunction, or unit breakdown. In the worst case, this 
could lead to a serious impediment to securing product 
safety.

■ 

Do not discharge the refrigerant into the atmosphere. 
If refrigerant leaks during installation, ventilate the 
room. Check that the refrigerant does not leak after 
installation has been completed.

 ,IUHIULJHUDQWOHDNVDQGFRPHVLQFRQWDFWZLWK¿UHRUKHDW

-

ing part of such a fan heater, kerosene heater, or cooking 
stove, it will create harmful gas.

■ 

Use appropriate tools and piping materials for instal-
lation.

 

The pressure of R32 is 1.6 times more than R22. Not using 
appropriate tools or materials and incomplete installation 
could cause the pipes to burst or injury. 

■ 

When pumping down the refrigerant, stop the com-
pressor before disconnecting the refrigerant pipes.

  If the refrigerant pipes are disconnected while the com-

pressor is running and the stop valve is open, air could be 
drawn in and the pressure in the refrigeration cycle could 
become abnormally high. This could cause the pipes to 
burst or injury.

■ 

When installing the unit, securely connect the refriger-
ant pipes before starting the compressor.

 

If the compressor is started before the refrigerant pipes are 
connected and when the stop valve is open, air could be 
drawn in and the pressure in the refrigeration cycle could 
become abnormally high. This could cause the pipes to 
burst or injury.

■ 

)DVWHQDÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HG

in this manual.

 ,IIDVWHQHGWRRWLJKWDÀDUHQXWPD\EUHDNDIWHUDORQJ

period and cause refrigerant leakage.

■ 

The unit shall be installed in accordance with national 
wiring regulations.

■ 

:KHQXVLQJDJDVEXUQHURURWKHUÀDPHSURGXFLQJ

equipment, completely remove all of the refrigerant 
from the air conditioner and ensure that the area is 
well-ventilated.

 ,I WKH UHIULJHUDQW OHDNV DQG FRPHV LQ FRQWDFW LQ ¿UH RU

heating part, it will create harmful gas and there is risk of 

¿UH

■ 

Do not use means to accelerate the defrosting process 
or to clean, other than those recommended by the 
manufacturer.

■ 

The appliance shall be stored in a room without 
continuously operating ignition sources (for exam-

SOHRSHQÀDPHVDQRSHUDWLQJJDVDSSOLDQFHRUDQ

operating electric heater.

■ 

Do not pierce or burn.

■ 

Be aware that refrigerants may not contain an odour.

■ 

Pipe-work shall be protected from physical damage.

■ 

The installation of pipe-work shall be kept to a mini-
mum.

■ 

Compliance with national gas regulations shall be 
observed.

■ 

Keep any required ventilation openings clear of ob-
struction.

■ 

In Australia, only technicians that possess the appro-
priate license issued by the Australian Refrigeration 
Council (ARC) should install this product.

   Install an earth leakage breaker depending on the 

installation place.

 

If an earth leakage breaker is not installed, it could cause 
electric shock.

  Perform the drainage/piping work securely according 

to the installation manual.

  If there is defect in the drainage/piping work, water could 

drop from the unit, soaking and damaging household goods.

 'RQRWWRXFKWKHDLULQOHWRUWKHDOXPLQXP¿QVRIWKH

outdoor unit.

 

This could cause injury. 

  Do not install the outdoor unit where small animals 

may live.

 

If small animals enter and touch the electric parts inside the 

XQLWLWFRXOGFDXVHDPDOIXQFWLRQVPRNHHPLVVLRQRU¿UH

Also, advise user to keep the area around the unit clean. 

MEANINGS OF SYMBOLS DISPLAYED ON INDOOR UNIT AND/OR OUTDOOR UNIT

Summary of Contents for MSZ-GL71VGD

Page 1: ...that there is no dust clogging or loose parts in both the outlet and the plug Make sure that the power supply plug is pushed completely into the outlet If there is dust clogging or loose parts on the power supply plug or the outlet it could cause electric shock or UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ replace it Attach the electrical cover to the indoor unit and the service panel to t...

Page 2: ...maldehyde etc which may cause chemical cracking 7KH DSSOLDQFH VKDOO EH VWRUHG VR DV WR SUHYHQW PHFKDQLFDO GDPDJH IURP RFFXUULQJ Pipe length and height difference Max pipe length 30 m Max height difference 15 m Max number of bends 6 7 10 Refrigerant adjustment A 8 20 g m Insulation thickness 9 10 8 mm INDOOR UNIT WARNING Install the indoor unit in rooms which exceed 3 1 m2 KHUH DLUÀRZ LV QRW EORFNH...

Page 3: ...to local code requirements To comply with the requirements of Australian standard AS NZS 3000 electrical installations wiring rules the electrical wiring required between the indoor and outdoor units must be installed by a licenced electrical contractor Check that cabling will not be subject to wear corrosion excessive pres sure vibration sharp edges or any other adverse environmental effects The ...

Page 4: ...the front panel 1 Open the front panel 2 Remove VA clamp 3 Pass indoor outdoor unit connecting wire A from the back of the indoor unit and process the end of the wire RRVHQ WHUPLQDO VFUHZ DQG FRQQHFW UVW WKH HDUWK ZLUH WKHQ LQGRRU RXWGRRU XQLW FRQ necting wire A to the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appear...

Page 5: ...and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening After tightening SXOO WKH ZLUHV OLJKWO WR FRQ UP WKDW WKH GR QRW PRYH 4 Connect power supply cord K 5 Fix indoor outdoor unit connecting wire A and power supply cord K with the cord clamp 6 Close the service panel securely 0DNH HDUWK ZLUH D OLWWOH OR...

Page 6: ...ompound pressure gauge for R32 R410A 0 101 MPa 760 mmHg Handle Low Handle High Adapter for preventing the EDFN ÀRZ Charge hose for R32 R410A Close Open Hexagonal wrench Precautions when using the control valve When attaching the control valve to the service port valve core may deform or loosen if excess pressure is applied This may cause gas leak Service port Body Close R32 Open Control valve A Wh...

Page 7: ...MPa Gauge approx 0 5 to 0 kgf cm2 6 Stop the emergency COOL operation Press the E O SW several times until all LED lamps turn off Refer to operating instruc tions for details 5 RELOCATION AND MAINTENANCE When pumping down the refrigerant stop the compressor before disconnecting the refrigerant pipes The compressor may burst if air etc get into it WARNING 5 2 REMOVING THE INDOOR UNIT Remove the bot...