
Burr
Copper pipe
Spare reamer
Pipe cutter
3-2. FLARING WORK
1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)
2) Completely remove all burrs from the cut cross section
of pipe. (Fig. 3)
• Put the end of the copper pipe to downward direction
as you remove burrs in order to avoid to let burrs drop
in the piping.
5HPRYHÀDUHQXWVDWWDFKHGWRLQGRRUDQGRXWGRRUXQLWV
then put them on pipe having completed burr removal.
1RWSRVVLEOHWRSXWWKHPRQDIWHUÀDULQJZRUN
)ODULQJZRUN)LJ)LUPO\KROGFRSSHUSLSHLQWKH
dimension shown in the table. Select A mm from the
table according to the tool you use.
&KHFN
&RPSDUHWKHÀDUHGZRUNZLWK)LJ
,IÀDUHLVQRWHGWREHGHIHFWLYHFXWRIIWKHÀDUHGVHFWLRQ
DQGGRÀDULQJZRUNDJDLQ
3-3. PIPE CONNECTION
)DVWHQÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKHWDEOH
:KHQIDVWHQHGWRRWLJKWÀDUHQXWPD\EUHDNDIWHUDORQJSHULRGDQGFDXVHUHIULJHUDQWOHDN
age.
• Be sure to wrap insulation around the piping. Direct contact with the bare piping may result
in burns or frostbite.
Indoor unit connection
&RQQHFWERWKOLTXLGDQGJDVSLSLQJVWRLQGRRUXQLW
$SSO\DWKLQFRDWRIUHIULJHUDWLRQRLO-RQWKHÀDUHGHQGVRIWKHSLSHV'RQRWDSSO\UHIULJHUD
WLRQRLORQVFUHZWKUHDGV([FHVVLYHWLJKWHQLQJWRUTXHZLOOUHVXOWLQGDPDJHRQWKHVFUHZ
)RUFRQQHFWLRQ¿UVWDOLJQWKHFHQWHUWKHQWLJKWHQWKH¿UVWWRWXUQVRIÀDUHQXWE\KDQG
8VHWLJKWHQLQJWRUTXHWDEOHDERYHDVDJXLGHOLQHIRULQGRRUXQLWVLGHXQLRQMRLQWVHFWLRQDQG
WLJKWHQXVLQJWZRZUHQFKHV([FHVVLYHWLJKWHQLQJGDPDJHVWKHÀDUHVHFWLRQ
Pipe diameter
(mm)
Nut
(mm)
A (mm)
7LJKWHQLQJWRUTXH
Clutch type
tool for
R32,R410A
Clutch type
tool
for R22
Wing nut
type tool
for R22
N•m
NJIFP
ø 6.35 (1/4”)
17
0 to 0.5
1.0 to 1.5
1.5 to 2.0
13.7 to 17.7 140 to 180
ø 9.52 (3/8”)
22
34.3 to 41.2 350 to 420
ø12.7 (1/2”)
26
2.0 to 2.5
49.0 to 56.4 500 to 575
ø15.88 (5/8”)
29
73.5 to 78.4 750 to 800
Copper
pipe
Good
Tilted Uneven Burred
No good
Fig. 1
Fig. 2
Clutch type
Flaring tool
Fig. 4
Fig. 3
Smooth all
around
Even length
all around
Inside is shin-
ing without any
scratches.
Flare nut
Die
Fig. 5
Fig. 6
3. OUTDOOR UNIT INSTALLATION
Copper pipe
Wing nut type
WARNING
When installing the unit, securely connect the refrigerant
pipes before starting the compressor.
3-1. CONNECTING WIRES FOR OUTDOOR UNIT
1) Open the service panel.
2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from
WKHLQGRRUXQLWFRUUHFWO\RQWKHWHUPLQDOEORFN%HFDUHIXOQRWWRPDNHPLVZLULQJ)L[
WKHZLUHWRWKHWHUPLQDOEORFNVHFXUHO\VRWKDWQRSDUWRILWVFRUHLVDSSHDUHGDQGQR
H[WHUQDOIRUFHLVFRQYH\HGWRWKHFRQQHFWLQJVHFWLRQRIWKHWHUPLQDOEORFN
3) Firmly tighten the terminal screws to prevent them from loosening. After tightening,
SXOOWKHZLUHVOLJKWO\WRFRQ¿UPWKDWWKH\GRQRWPRYH
4) Connect power supply cord (K).
5) Fix indoor/outdoor unit connecting wire (A) and power supply cord (K) with the cord clamp.
6) Close the service panel securely.
0DNHHDUWKZLUHDOLWWOHORQJHUWKDQRWKHUV0RUHWKDQPP
• For future servicing, give extra length to the connecting wires.
• Be sure to attach each screw to its correspondent terminal when securing the cord
DQGRUWKHZLUHWRWKHWHUPLQDOEORFN
35 mm
15 mm
Lead wire
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit in the
same manner applied for indoor unit.
)RUWLJKWHQLQJXVHDWRUTXHZUHQFKRUVSDQQHUDQGXVHWKH
VDPHWLJKWHQLQJWRUTXHDSSOLHGIRULQGRRUXQLW
3-4. INSULATION AND TAPING
1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using piping tape (G), apply taping starting from the entry of outdoor unit.
• Stop the end of piping tape (G) with tape (with adhesive agent attached).
• When piping have to be arranged through above ceiling, closet or where the temperature
and humidity are high, wind additional commercially sold insulation to prevent condensa-
tion.
WARNING
7RDYRLGULVNRI¿UHÀDUHFRQQHFWLRQVKRXOGEHLQVWDOOHGRXWGRRUV
5HXVDEOHPHFKDQLFDOFRQQHFWRUVDQGÀDUHGMRLQWVDUHQRWDOORZHGLQGRRUV
:KHQFRQQHFWLQJWKHUHIULJHUDQWSLSLQJE\EUD]LQJUDWKHUWKDQXVLQJÀDUHFRQQHFWLRQV
complete all brazing prior to connecting indoor unit to outdoor unit.
Power supply cord (K)
This unit has demand response capability which is compliant with AS/NZS 4755.3.1.
7RDFWLYDWHWKLVIXQFWLRQ\RXQHHGWRPDNHDFRQWUDFWZLWKUHPRWHDJHQWVVXFKDV
electric supply company, then this unit should be connected to Demand response en-
abling devise (DRED). For further information, consult your dealer. This unit supports
3 Demand Response Modes (DRMs): DRM1, DRM2 and DRM3.
CAUTION
• To prevent malfunction caused by noise, route the cord connecting this unit to
DRED and the power supply cord as parallel as possible.
'RQRWFRQQHFWWKHGHPDQGFRQWUROWUDQVPLVVLRQFDEOHWRWKHWHUPLQDOEORFNIRU
power supply.
• Do not pull, extremely bend or apply strong pressure on the wire to prevent failure.
• Do not screw DRED to outdoor unit.
• Do not put DRED in outdoor unit.
• Secure electrical wiring above clamp.
• Do not get DRED wire caught in the service panel.
1 2 3 C
7HUPLQDOEORFN
Cord clamp
Cable strap
The tip should be
pointed to the left side.
Power supply
cord (K)
Indoor/outdoor
unit connecting
wire (A)
1 : DRM 1
2 : DRM 2
3 : DRM 3
C : COMMON
AS/NZS4755
WHUPLQDOEORFN
Wire saddle
This unit has demand response capability which is compliant with AS/NZS 4755.3.1.
7RDFWLYDWHWKLVIXQFWLRQ\RXQHHGWRPDNHDFRQWUDFWZLWKUHPRWHDJHQWVVXFKDV
electric supply company, then this unit should be connected to Demand response en-
abling devise (DRED). For further information, consult your dealer. This unit supports
3 Demand Response Modes (DRMs): DRM1, DRM2 and DRM3.
CAUTION
• To prevent malfunction caused by noise, route the cord connecting this unit to
DRED and the power supply cord as parallel as possible.
'RQRWFRQQHFWWKHGHPDQGFRQWUROWUDQVPLVVLRQFDEOHWRWKHWHUPLQDOEORFNIRU
power supply.
• Do not pull, extremely bend or apply strong pressure on the wire to prevent failure.
• Do not screw DRED to outdoor unit.
• Do not put DRED in outdoor unit.
• Secure electrical wiring above clamp.
• Do not get DRED wire caught in the service panel.