Check of outdoor thermistor
Measure
resistance
between CN 661
1
and
2
.
No
Yes
Replace the
thermistor.
Defrost thermistor (RT61)
Re-connect CN661.
Turn ON the power
supply and press
the EMERGENCY
OPERATION
switch.
Does the resistance
of thermistor have
the characteristics
on page 41?
No
Yes
Does the unit operate
10 minutes or more?
Replace the deicer P.C.
board.
Ok
❈
3
❈
3 Defective contact of the connector is considered.
Turn OFF the
power supply.
G
Check of R.V. coil
H
After 3 minutes, does the unit
operate in COOL mode?
OK
Yes
Yes
No
After 3 minutes, does the unit
operate in HEAT mode?
OK
No
Replace the
deicer P.C. board
No
Replace the R.V. coil.
Turn ON the power supply and operate
the indoor unit in HEAT mode by pressing
the EMERGENCY OPERATION switch.
Is there 220-240V AC
between CN721
1
–
2
on the
deicer P.C. board?
Refer to page 50.
Replace the
deicer P.C. board.
Yes
Yes
Yes
No
Replace the R.V. coil.
Turn ON the power supply and operate
the indoor unit in COOL mode by pressing
the EMERGENCY OPERATION switch.
Is there 220-240V AC
between CN721
1
–
2
on the
deicer P.C. board?
Refer to page 50.
Unit operates COOL mode even if it is set to HEAT mode.
w
First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
Unit operates HEAT mode even if it is set to COOL mode.
w
First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
W
Disconnect the connector CN661 from the deicer P.C. board.
(Check the characteristics of thermistor.)
Check of R.V. coil
H
When OPERATION INDICATOR lamp flashes 6-time.
Thermistors in the outdoor unit are abnormal.