Check of remote controller and receiver P.C. board
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but doesn’t operate with the remote controller.
Yes
Replace the batteries. (Refer to 9-1-4.)
Turn on a radio to AM and press switch
on the remote controller.
Is noise heard from radio?
Are there any fluorescent lights of
inverter or rapid-start type within
the range of 1m?
Replace the remote controller.
• Reinstall the unit away from lights.
• Attach a filter on receiving part.
Switch on the remote controller.
Is LCD display on the remote con-
troller displayed?
Remove batteries, then set them back and press the RESET
button. Check if the unit operates with the remote controller.
Yes
Does the unit operate with the
remote controller?
Yes
OK
No
(not clear)
Yes
No
No
Yes
Measure the voltage between receiver P.C. board connector CN302
No.3
(–)
and No.5
(+)
when the remote controller button is pressed.
Is the voltage approx. 4V DC?
Replace the indoor electronic control
P.C. board.
Replace the power monitor, receiver P.C. board.
No(5V or 0V DC)
No
w
Check the remote controller is exclusive for this air conditioner.
C
C
Check of indoor electronic control P.C. board
Check the both “parts side” and “pattern
side” of indoor electronic control P.C.
board visually.
Replace the fuse.
Is fuse (F11) blown?
Be sure to check both fuse
and varistor in any case.
Replace the fan motor.
Replace the indoor
electronic control
P.C. board.
Is winding
resistance of
fan motor 0
"
?
Is winding
resistance of
vane motor 0
"
?
No
Yes
Replace the vane
motor.
No
Yes
Yes
Is varistor (NR11) burnt?
Replace the varistor.
Yes
Turn OFF the power supply.
Remove indoor fan motor connector CN211 and
vane motor connector CN151 from the indoor electronic
control P.C. board and turn ON the power supply.
No
Does the unit operate with the remote controller?
Does the OPERATION INDICATOR lamp light up
by pressing the EMERGENCY OPERATION switch?
Yes
No
Be sure to check both resistances.
Turn OFF the
power supply.
Turn OFF the
power supply.
No
The unit doesn’t operate with the remote controller.
Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.