Mitsubishi Electric MS12 Installation Manual Download Page 7

Drain hose

Drain cap

Drain cap

Drain hose

Downward
slope

Water
leakage

Do not raise.

Water
leakage

Accumulated
drain water

Waving

Water
leakage

Tip of drain
hose dipped
in water.

Ditch

Air

Drain
hose

Cut off in case of left piping.

Use a bandage stopper at
the end of felt tape 

7

.

Be careful drain
hose is not heaved.

Drain cap

FOR LEFT OR LEFT-REAR PIPING

Pipe arrangement
Put the refrigerant piping and the drain hose together, then apply felt tape 

7

 to

them.

REATTACHING DRAIN HOSE

Be sure to reattach the drain hose and the drain cap in case of left or left-rear piping.
Otherwise, it could cause drops of water to drip down from the drain hose.

1 Pull out the drain cap at the rear right of the indoor unit.

Hold the convex section at the end and pull the drain cap.

2 Pull out the drain hose at the rear left of the indoor unit.

Hold the claw marked by the arrow and pull out the drain hose forward.

3 Put the drain cap into the section to which the drain hose is to

be attached at the rear of the indoor unit.

Insert the screwdriver, etc. (not sharp-edged tool) into the hole at the end of the cap
and insert the cap fully into the drain pan.

4 Insert the drain hose into the section to which the drain hose is

to be attached at the rear right of the indoor unit.

Insert the drain hose fully into the drain pan. Check if the hose is hooked securely to
the projection of its inserting part at the drain pan.

INDOOR UNIT INSTALLATION

Insert the drain hose into the wall hole sleeve 

C

, and hook the upper part of

indoor unit on the installation plate 

1

. Then, move the unit to the very edge of the

left side for putting the piping easily in the back space of the indoor unit.

Connect the refrigerant piping with the extension pipe 

B

.

Thrust the lower part of the indoor unit into the installation plate 

1

.

4-6 DRAIN PIPING

The drain hose should point downward for easy drain flow. (Fig. 1)
Do not make drain piping as shown in Fig. 2 to 5.

(Fig. 1)

(Fig. 2)

(Fig. 3)

(Fig. 4)

(Fig. 5)

If the drain hose provided with the indoor unit is too short, connect it with drain
hose

I

 that should be provided at your site.

If the extension drain hose has to pass through a room, be sure to wrap it with
commercially sold insulation.

Felt tape 

7

Firmly apply felt tape 

7

 from the end.

(Felt tape 

7

 overlap width should be 1/3

the tape width.)

Drain hose

Bead

Installation
plate

1

The polystyrene block is
provided in the packing
material.

Set the polystyrene block along the “L” formed bead of
the installation plate to hold the unit obliquery.

Less than
2 in. gap

Soft hose
I.D.
19/32 in.
or hard
vinyl
chloride

Summary of Contents for MS12

Page 1: ... main power in case of setting up the indoor electronic control P C board or wiring works It could cause an electric shock CAUTION Ground the unit Do not connect the ground to a gas pipe water pipe lightning rod or telephone ground Defective grounding could cause an electric shock Do not install the unit in a place where an inflammable gas leaks If gas leak and accumulate in the area surrounding t...

Page 2: ...s on both indoor and outdoor sides Remove the valve cover of the outdoor unit then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Limits Pipe length 49 ft max Height difference 25 ft max No of bends 10 max Refrigerant adjustment If pipe length exceeds 25 ft additional refrigerant R 22 charge is required The outdoor unit is charged with refrigerant for pipe leng...

Page 3: ...te controller Wireless Indoor unit Outdoor unit DC12V Polar ELECTRICAL SPECIFICATIONS MODEL MSH12TN MSH15TN INDOOR UNIT Power supply V PHASE Hz 115 1 60 115 1 60 Min Circuit Ampacity 0 6 0 6 Fan motor F L A 0 43 0 43 OUTDOOR UNIT Power supply V PHASE Hz 208 230 1 60 208 230 1 60 Max Fuse size time delay A 15 20 Min Circuit Ampacity 14 14 Fan motor F L A 0 42 0 52 Compressor R L A 10 0 10 0 L R A 3...

Page 4: ...rminal MU12TN and MUH12TN MU15 17TN and MUH15TN Conduit cover Connector Lock nut Service panel Grounding terminal Connect wires to the matching numbers of terminals Remark Indoor unit can also be powered from an independent power supply Max Fuse size time delay 15 A In this case these indoor outdoor connecting wires for indoor power supply are not necessary A disconnect switch may be required Chec...

Page 5: ...at the same time that a power has restored If the unit has been off with the remote controller before power failure the auto restart function does not work as the power button of the remote controller is off To prevent breaker off due to the rush of starting current systematize other home appliances not to turn on at the same time 4 5 PIPE FORMING Place the drain hose below the refrigerant piping ...

Page 6: ...the same method as the indoor unit For tightening use the same tightening torque applied for indoor unit and tighten the flare nut with torque wrench or spanner INSULATION AND TAPING 1 Cover piping joints with pipe cover 2 For outdoor unit side surely insulate every piping including valves 3 Using piping tape G apply taping starting from the entry of outdoor unit Fix the end of piping tape G with ...

Page 7: ... to which the drain hose is to be attached at the rear right of the indoor unit Insert the drain hose fully into the drain pan Check if the hose is hooked securely to the projection of its inserting part at the drain pan INDOOR UNIT INSTALLATION Insert the drain hose into the wall hole sleeve C and hook the upper part of indoor unit on the installation plate 1 Then move the unit to the very edge o...

Page 8: ...rated with the remote controller both the test run and the emergency operation are released by commands from the remote controller Once the compressor stops the restart preventive device operates so the compressor will not operate for three minutes to protect the air conditioner 6 5 EXPLANATION TO THE CUSTOMER Using the OPERATING INSTRUCTIONS explain the following to the customer how to control te...

Reviews: