13
9-3. Troubleshooting check table
• The following indication applies regardless of shape of the indicator.
Operation Indicator
Lighted
Not lighted
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.
Self check table
NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with the
OPERATION INDICATOR lamp flashing.
No.
1
2
4
5
6
Symptom
Operation indicator lamp
Detection method
Checkpoint
0.5-second ON
0.5-second OFF
MS-GA80VB
Mis-Wiring
MU-GA80VB
Outdoor
thermistor
MU-GA80VB
Outdoor
control
system
Indoor coil
thermistor
3 minutes after power supply turns ON, when
serial signal is not received.
<Thermistor short>
Thermistors are abnormal when they short
after compressor start-up.
<Thermistor open>
Thermistors are abnormal when they open
after compressor start-up.
However, discharge temperature thermistor is
abnormal when open circuit is detected more
than 10 minutes after compressor start-up.
When it cannot properly read data in the
nonvolatile memory of the deicer P.C. board,
outdoor unit stops.
• Check the deicer P.C.
board.
• Reconnect the connector.
Refer to "Check of outdoor
thermistor". Refer to service
manual OB370.
• Check the deicer P.C. board.
Refer to service manual
OB370.
• Refer to 9-5.
D
"How to check
mis-wiring ".
3
Indoor fan
motor
7
MU-GA80VB
Low
discharge
tempera-
ture
protection
When discharge temperature has been 50
:
or less on cool operation.
Abnormal
point
Outdoor unit
does not
operate.
Room
temperature
thermistor
2-time flash
2.5-second OFF
Detect Indoor coil/room temperature
thermistor short or open circuit every 8
seconds during operation.
• Refer to the characteristics of
main indoor coil thermistor,
sub indoor coil thermistor,
and room temperature on
page 18.
3-time flash
2.5-second OFF
Indoor fan repeats
12 seconds ON
and 3minutes OFF.
When the indoor
fan breaks, the
fan keeps stopping.
When rotational frequency feedback signal is
not emitting during 12-second indoor fan
operation.
• Refer to 9-5.
A
"Check of
indoor fan motor".
4-time flash
2.5-second OFF
Indoor
control
system
When it cannot properly read data in the
nonvolatile memory of the indoor electronic
control P.C. board.
Outdoor unit
does not
operate.
Outdoor unit
does not
operate.
• Check the indoor electronic
control P.C. board.
6-time flash
2.5-second OFF
• Refer to "Check of LEV".
• Check refrigerant circuit and
refrigerant amount.
Refer to service manual
OB370.
Outdoor unit
does not
operate.
Outdoor unit
does not
operate.
Outdoor unit
does not
operate.
7-time flash
2.5-second OFF
10-time flash
2.5-second OFF
· Flashing of the OPERATION INDICATOR lamp (on the left-hand side) indicates possible
abnormalities.
· The OPERATION INDICATOR lamp (on the left-hand side) is lighted during normal operation.
OB369-1.qxp 04.10.14 1:37 PM Page 13