24
In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the
heat exchanger, and when temperature difference develops, the indoor coil thermistors adjust LEV opening to diminish the
super heat. This action is called Evaporation Temperature Protection.
Indoor heat
exchanger
(MXZ-3A30NA)
Outdoor
heat
exchanger
Exclusive
LEV
Receiver
LEV
Receiver
The opening pulse of the Receiver LEV is fixed to the standard No.3 in cooling operation, and so is that of each Exclusive
LEV in heating operation.
However the opening pulse will be changed to the standard No.4 or No.5 when the discharge temperature protection or high-
pressure protection is working.
In addition to that, it will also be changed to standard No.2 or No.1 when the opening pulse of the each Exclusive LEV
becomes 100 pulse or less in cooling operation or so does that of Receiver LEV in heating operation.
MXZ-2A20NA/3A30NA
The table below shows the role of Exclusive LEV and Receiver LEV in each operation mode.
Circulation Amount
Control
Capacity Distribution
Discharge
Temperature
Protection
High Pressure
Protection
Evaporation
Temperature
Protection
COOL
Exclusive LEV
○
○
○
○
○
Receiver LEV
×
×
○
○
○
HEAT
Exclusive LEV
×
○
○
○
—
Receiver LEV
○
×
○
○
—
<MXZ-2A20NA>
Number of
operating
indoor units
Standard No.
LEV opening (pulse)
COOL HEAT
1 unit
2 units
1 unit
2 units
1
200
150
120
120
2
300
320
140
140
3
400
360
160
160
4
450
410
220
220
5
500
500
280
280
<MXZ-3A30NA>
Number of
operating
indoor units
Standard No.
LEV opening (pulse)
COOL HEAT
1 unit
2 units
3 units
1 unit
2 units
3 units
1
150
250
250
250
250
250
2
250
320
320
300
300
300
3
350
360
370
450
380
380
4
400
410
420
460
400
390
5
450
460
470
470
450
440