MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER
11-1. HOW TO "MONITOR THE OPERATION DATA"
Refer to "14-10. REQUEST CODE" when monitoring the operation data.
Certain indoor/outdoor combinations do not have the request code function; therefore, no request codes are displayed.
Request code
Request content
Description
(Display range)
Unit
Remarks
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
Operation state
Compressor-Operating current (rms)
Compressor-Accumulated operating time
Compressor-Number of operation times
Discharge temperature (TH4)
Outdoor unit - Liquid pipe temperature
Outdoor unit-2-phase pipe temperature (TH6)
Outdoor unit-Ambient temperature (TH7)
Outdoor unit-Heatsink temperature (TH8)
Discharge superheat (SHd)
Comp. Surface temperature
Compressor-Operating frequency
Compressor-Target operating frequency
Outdoor unit-Fan output step
Outdoor unit-Fan 1 speed
(Only for air conditioners with DC fan motor)
Outdoor unit-Fan 2 speed
(Only for air conditioners with DC fan motor)
LEV (B) opening
LEV (A) opening
Primary current
DC bus voltage
Number of connected indoor units
Indoor unit-Setting temperature
Indoor unit-Intake air temperature <Measured by thermostat>
Indoor unit-Intake air temperature (Unit No. 1)
Indoor unit-Intake air temperature (Unit No. 2)
Indoor unit-Intake air temperature (Unit No. 3)
Indoor unit-Intake air temperature (Unit No. 4)
Indoor unit - Liquid pipe temperature (Unit No. 1)
Indoor unit - Liquid pipe temperature (Unit No. 2)
Indoor unit - Liquid pipe temperature (Unit No. 3)
Indoor unit - Liquid pipe temperature (Unit No. 4)
Indoor unit-Cond./Eva. pipe temperature (Unit No. 1)
Indoor unit-Cond./Eva. pipe temperature (Unit No. 2)
Indoor unit-Cond./Eva. pipe temperature (Unit No. 3)
Indoor unit-Cond./Eva. pipe temperature (Unit No. 4)
Thermostat ON operating time
Test run elapsed time
Refer to "11-2-1.Detail Contents in Request Code".
0 – 50
0 – 9999
0 – 9999
3 – 217
-48 – 90
-39 – 88
-39 – 88
-40 – 200
0 – 255
-20 – 221
0 – 255
0 – 255
0 – 10
0 – 9999
0 – 9999
0 – 500
0 – 500
0 – 50
180 – 370
0 – 4
17 – 30
8 – 39
8 – 39
8 – 39
8 – 39
8 – 39
-39 – 88
-39 – 88
-39 – 88
-39 – 88
-39 – 88
-39 – 88
-39 – 88
-39 – 88
0 – 999
0 – 120
–
A
10 hours
100 times
°C
°C
°C
°C
°C
°C
°C
Hz
Hz
Step
rpm
rpm
Pulses
Pulses
A
V
Units
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
Minutes
Minutes
"0" is displayed if the air conditioner is a single-fan
type.
"0" is displayed if the target unit is not present.
"0" is displayed if the target unit is not present.
"0" is displayed if the target unit is not present.
Not possible to activate maintenance mode during the test run.
<Heat mode-4-°C correction>
<Heat mode-4-°C correction>
<Heat mode-4-°C correction>
<Heat mode-4-°C correction>
11-2. Request code list
Summary of Contents for MR. SLIM PUZ-M100VKA2
Page 17: ...17 OCH773 5 OUTLINES AND DIMENSIONS Unit mm ...
Page 18: ...18 OCH773 6 WIRING DIAGRAM PUZ M100VKA2 ET ER TH ...
Page 19: ...19 OCH773 PUZ M125VKA2 ET ER TH PUZ M140VKA2 ET ER TH ...
Page 20: ...20 OCH773 PUZ M100YKA2 ET ER TH PUZ M125YKA2 ET ER TH PUZ M140YKA2 ET ER TH ...
Page 115: ...115 OCH773 ...