
34
OCH773
Check code Abnormal point and detection method
Cause
Judgment and action
U9
(4220)
Detailed
codes
To find out the detail history (latest) about U9 error, turn ON SW2-1, 2-2 and 2-6.
Refer to "9-9. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS".
01
Overvoltage error
• Increase in DC bus voltage to
PUZ-M·VKA2: 430 V
PUZ-M·YKA2: 760 V
1
Abnormal increase in power source
voltage
2
Disconnection of compressor wiring
3
Defective outdoor power circuit
board
4
Compressor has a ground fault.
1
Check the field facility for the power
supply.
2
Correct the wiring (U
.V.W phase) to
compressor. Refer to "9-8. TEST POINT
DIAGRAM
(Outdoor power circuit board)".
3
Replace outdoor power circuit board.
4
Check compressor for electrical insula-
tion. Replace compressor.
02
Undervoltage error
• Instantaneous decrease in DC
bus voltage to
PUZ-M·VKA2: 200 V
PUZ-M·YKA2: 350 V
1
Decrease in power source voltage,
instantaneous stop.
2
Defective converter drive circuit in
outdoor power circuit board (
PUZ-
M·VKA2)
3
Defective 52C drive circuit in outdoor
power circuit board
4
Disconnection or loose connection
of rush current protect resistor RS
(PUZ-M·YKA2)
5
Defective rush current protect
resistor RS (PUZ-M·YKA2)
6
Disconnection or loose connection
of CN2 on the outdoor power circuit
board /controller circuit board (PUZ-
M·VKA2)
7
Power circuit failure on DC supply for
15 V DC output on outdoor controller
circuit board (PUZ-M·VKA2)
1
Check the field facility for the power
supply.
2
Replace outdoor power circuit board.
(PUZ-M·VKA2)
3
Replace outdoor power circuit board.
4
Check RS wiring. (
PUZ-M·YKA2)
5
Replace RS. (PUZ-M·YKA2)
6
Check CN2 wiring. (
PUZ-M·VKA2)
7
Replace outdoor controller circuit board.
(PUZ-M·VKA2)
04
Input current sensor error/
L1-phase open error
• Decrease in input current
through outdoor unit to 0.1 A
only if operation frequency is
more than or equal to 40 Hz
or compressor current is more
than or equal to 6 A.
1
L1-phase open (PUZ-M·YKA2)
2
Disconnection or loose connection
between TB1 and outdoor noise filter
circuit board (PUZ-M·YKA2)
3
Disconnection or loose connection
of CN5 on the outdoor power circuit
board/CNCT on the outdoor noise
filter board (PUZ-M·YKA2)
4
Defective ACCT (AC current trans)
on the outdoor noise filter circuit
board (PUZ-M·YKA2)
5
Defective input current detection
circuit in outdoor power circuit board
6
Defective outdoor controller circuit
board
1
Check the field facility for the power
supply. (PUZ-M·YKA2)
2
Check the wiring between TB1 and
outdoor noise filter circuit board. (PUZ-
M·YKA2)
3
Check CN5/CNCT wiring. (
PUZ-
M·YKA2)
4
Replace outdoor noise filter circuit
board. (PUZ-M·YKA2)
5
Replace outdoor power circuit board.
6
Replace outdoor controller circuit board.
08
Abnormal power synchronous
signal
• No input of power synchronous
signal to power circuit board
• Power synchronous signal
of 44 Hz or less, or 65 Hz or
more is detected on power
circuit board.
1
Distortion of power source voltage,
noise superimposition.
2
Disconnection or loose connection
of earth wiring
3
Disconnection or loose connection
of CN2 on the outdoor power circuit
board /controller circuit board
4
Defective power synchronous signal
circuit in outdoor controller circuit
board
5
Defective power synchronous signal
circuit in outdoor power circuit board
1
Check the field facility for the power
supply.
2
Check earth wiring.
3
Check CN2 wiring.
4
Replace outdoor controller circuit board.
5
Replace outdoor power circuit board.
Continue to the next page.
Summary of Contents for MR. SLIM PUZ-M100VKA2
Page 17: ...17 OCH773 5 OUTLINES AND DIMENSIONS Unit mm ...
Page 18: ...18 OCH773 6 WIRING DIAGRAM PUZ M100VKA2 ET ER TH ...
Page 19: ...19 OCH773 PUZ M125VKA2 ET ER TH PUZ M140VKA2 ET ER TH ...
Page 20: ...20 OCH773 PUZ M100YKA2 ET ER TH PUZ M125YKA2 ET ER TH PUZ M140YKA2 ET ER TH ...
Page 115: ...115 OCH773 ...