89
Function
Settings
Mode No.
No.
Setting
: Initial setting (Factory setting)
- : Not available
4-Way
cassette
Ceiling
suspended
Wall mounted
PCA-KA
PKA-HA(L)
PKA-KA(L)
Filter sign
100h
1
2500h
07
(107)
2
"Clean the filter" indicator is not displayed
3
Air flow
Quiet
1
-
(Fan speed)
Standard
08
(108)
2
High ceiling
3
No.of air outlets
4 directions
1
-
-
3 directions
09
(109)
2
-
-
2 directions
3
-
-
Optional high efficiency
Not supported
10
(110)
1
-
filter
Supported
2
-
Vane setting
No vanes (Vane No.3 setting : PLA only)
1
-
Vane No.1 setting
11
(111)
2
-
Vane No.2 setting
3
-
Optional humidifier
Not supported
13
(113)
1
-
-
(PLA only)
Supported
2
-
-
Vane differential setting
No.1 setting (TH5: 75-82°F (24-28
))
1
in heating mode
No.2 setting (Standard, TH5: 82-90°F (28-32
))
14
(114)
2
(cold wind prevention)
No.3 setting (TH5: 90-100°F (32-38
))
3
Swing
23
(123)
1
2
Set temperature in heating
24
(124)
1
mode (4 deg up) *1
2
Fan speed when the
Extra low
1
heating thermostat is OFF
Stop
25
(125)
2
Keeping fan speed set by remote controller
3
Fan speed when the
Keeping fan speed set by remote controller
27
(127)
1
cooling thermostat is OFF
Stop
2
Detection of abnormality of
Detect
28
(128)
1
the pipe temperature (P8)
*1. PKA-HA(L)/KA(L): 3.6°F (2°C) up.
Neglect
2
-
-
-
-
-
-
-
-
-
-
-
PLA-BA
Not available Swing
Available
Wave air flow
Available
Not available
}
PLA-BA
Wired remote controller
(RF thermistor)
(2) Functions available when setting the unit number to 01-03 or AL (07 in case of IR wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to
4
setting the
indoor unit number.
• When setting functions for a simultaneous twin indoor unit system, set the unit number to 01 to 03 for each indoor unit in
case of selecting different functions for each unit referring to
4
setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin-indoor unit system, set refrigerant address to AL (07 in
case of IR wireless remote controller) referring to
4
setting the indoor unit number.
Mode No.11
Setting No. Settings
PLA-BA
PCA-KA
1
No Vanes
Vane No.3 setting
( Downward position than the standard )
Less smudging
No vane function
2
Vane No.1 setting
Standard
Standard
3
Vane No.2 setting
( Upward position than the standard )
Less draft *
( Upward position than the standard )
Less draft *
* Be careful of the smudge on ceiling.
Wired remote controller
(RF thermistor)
Wired remote controller
(RF thermistor)
Function
Settings
Mode No.
No.
Setting : Initial setting
(Factory setting)
Filter sign
100h
1
2500h
07
(107)
2
No filter sign indicator
3
External static pressure
5/15/35/50Pa
(0.02/0.06/0.14/0.20in.WG)
08
(108)
10
(110)
1
2
Extra low
3
Fan speed during the
heating thermo OFF
Stop
25
(125)
1
Set fan speed
2
27
(127)
1
2
Detection of abnormality
of the pipe temperature (P8)
1
28
(128)
2
Set temperature in heating
24
(124)
mode (4 deg up)
Refer to the right table
Refer to the right table
Available
Not available
Fan speed during the
cooling thermo OFF
Set fan speed
Stop
Available
Not available
External static
pressure
Setting No.
Initial setting
(Factory setting)
5Pa (0.02in.WG)
15Pa (0.06in.WG)
35Pa (0.14in.WG)
50Pa (0.20in.WG)
1
1
2
3
Mode No.
8 (108)
2
1
1
1
10 (110)
PEA-AA
OCH481C