64
11-9. TEST POINT DIAGRAM
Outdoor controller circuit board
PUZ-A18/24/30/36/42NHA4 PUZ-A18/24/30/36/42NHA4-BS
PUY-A12/18/24/30/36/42NHA4 PUY-A12/18/24/30/36/42NHA4-BS
PUZ-A18NHA4R1 PUY-A12/18NHA4R1
PUZ-A18NHA4R1-BS PUY-A12/18NHA4R1-BS
<CAUTION> TEST POINT
1
is high voltage.
Communication power supply
D71 Voltage
24V DC
CNS
S1-S2: A208/230V AC
CNAC
2
to
4
:
Power supply for out-
door controller circuit
board (208V-230V AC)
1
to
3
:
Power supply for indoor
and outdoor unit con-
nection wire
(208/230V AC)
CNF1, CNF2
Connect to the fan motor
1
-
4
: 280V DC
5
-
4
: 15V DC
6
-
4
: 0-6.5V DC
7
-
4
: 15V DC (When stopped)
7.5V DC (When operated)
(0V-15V pulse) (CNF2 is only for A42)
21S4
Four-way valve
<PUZ only>
63H
High pressure switch
SV2
Bypass valve
<A24/30/36 only>
CN4
Transmission to out-
door power circuit
board (CN4)
SW4
Test operation
SW6
Model select
SW5
Function switch
SW1
Forced defrost, detect history record reset, refrigerant address
CNDM
1
to
2
:
Input of low-level
sound priority mode
1
to
3
:
Input of external con-
tact point
TH4
Thermistor <Discharge>
<A42 only>
TH3
Thermistor
<Outdoor pipe>
TH7/6
Thermistor
<Outdoor/2-phase pipe>
CNDC
280V DC (
1
+,
3
-)
(Outdoor power circuit
board)
+ -
V
FG
(TEST POINT
4
)
(Voltage between
right pins of PC5C
and PC5D, pin 3
and pin 4)
(Same as
(CNF1
7
(+)-
4
(-))
V
SP
(TEST POINT
3
)
(Voltage between pins
of C5A, C5B):
DC 0V (when stopped),
DC 1– 6.5V
(when operated)
SW7
Demand control setting
CN51
External signal output
• Compressor operating
signal
• Abnormal signal
LEV-A
Linear expansion
valve
SWP
Pump down
SW8
Wiring replace
CNM
Connect to A control
service tool
CNMNT
Connect to
M-NET adapter (CN5)
CNVMNT
Connect to
M-NET adapter (CND)
CN2
Connect to the outdoor
power circuit board (CN2)
1
-
5
: Reception from
power circuit board
2
-
5
: Zero cross signal
(0-5V
DC)
3
-
4
: 18V DC
6
-
5
: 16V DC
7
-
5
: 16V DC
CN52C
(Connect to the noise
filter circuit board
(CN52C))
63L
Low pressure switch
TH32
Thermistor <Shell>
<except for A42>
OCH481C