96
OPERATING PROCEDURE
PHOTOS
Photo 17
Photo 16
16. Removing the accumulator
(1) Remove
• Service panel (see photo 1).
• Electrical parts box (see photo 6).
• 2 electrical parts box leg fixing screws (5
o
10), then electrical
parts box legs (see photo 6).
• 2 lower fixing screws (5
o
10) of the heat sink duct.
• 2 screws (4
o
10) which hold the metal plate above the heat
sink, then remove the plate.
• Fan guard.
• 3 upper fixing screws (5
o
10) of the heat sink duct located
below the fan motor, then remove the hear sink duct (see
photo 15).
(2) Collect the refrigerant.
(3) Disengage 2 welded points of the accumulator inlet and outlet
(see photo 17).
(4) Remove 4 accumulator fixing screws (5
o
10), then take out the
accumulator.
Note 1: Collect the refrigerant without releasing in the air.
Note 2: The welded points can be accessed easily by remov-
ing the rear panel. When servicing from the rear side,
remove the rear panel first, then follow the procedure
from number 2 (collecting the refrigerant) mentioned
above (see photo 16).
Fan motor
Upper heat sink duct fixing screw (3pcs)
Accumulator
Accumulator
fixing screw
(4pcs)
<Viewed from rear side>
OC338B-4.qxp 06.7.11 10:56 AM Page 96