37
12-5. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
Factor
Countermeasure
1. Remote controller display does not
work.
2. “PLEASE WAIT” display is remained
on the remote controller.
3. When pressing the remote controller
operation switch the OPERATION
display is appeared but it will be
turned off soon.
1
After cancelling to select function from the remote
controller, the remote controller operation switch will
be not accepted for approx. 30 seconds.
1
Normal operation
1
At longest 2 minutes after the power supply “PLEASE
WAIT” is displayed to start up.
2
Communication error between the remote controller
and indoor unit.
3
Communication error between the indoor and outdoor
unit.
4
Outdoor unit protection device connector is open.
1
DC12V is not supplied to remote controller.
(Power supply display is not indicated on LCD.)
2
DC12~15V is supplied to remote controller, however,
no display is indicated.
• “PLEASE WAIT” is not displayed.
• “PLEASE WAIT” is displayed.
1
Check LED2 on indoor controller circuit
board.
(1) When LED2 is lit.
Check the remote controller wiring for
breaking or contact failure.
(2) When LED2 is blinking.
Check short circuit of remote controller
wiring.
(3) When LED2 is not lit.
Refer to No.3 below.
2
Check the following.
• Failure of remote controller if “PLEASE
WAIT” is not displayed
• Refer to No.2 below if “PLEASE WAIT” is
displayed.
1
Normal operation
2
Self-diagnosis of remote controller
3
“PLEASE WAIT” is displayed for 6 minutes
at most. In case of indoor/outdoor unit
communication error. Check LED3 on
indoor controller board.
(1)When LED3 is not blinking.
Check indoor/outdoor connecting wire
for mis-wiring.
(Converse wiring of S1 and S2, or
break of S3 wiring.)
(2)When LED3 is blinking.
Indoor/outdoor connecting wire is nor-
mal.
4
Check LED display on outdoor controller
circuit board. Refer to 12-10.
Check protection device connector (63L
and 63H) for contact failure.
Refer to 12-9.
Error Code
Meaning of error code and detection method
Case
Judgment and action
A8
(6608)
M-NET•NO RESPONSE
Abnormal if a massage was transmitted
and there were reply (ACK) that massage
was received, but response command
does not return. Transmitting side detects
abnormality every 30 seconds, six times
continuously.
Note) The address and attribute displayed
at remote controller is indicate the
controller that did not reply (ACK).
1
Transmitting condition is
repeated fault because of
noise and the like.
2
Extension of transmission wire
voltage and signal is caused
by over-range transmission
wire.
• Maximum distance ······200m
• Remote controller line ··(12m)
3
Extension of transmission wire
voltage and signal is caused
by type-unmatched transmis-
sion wire.
Type ······
With shield wire-
CVVS, CPEVS
With normal wire (no shield)-
VCTF, VCTFK, CVV
CVS, VVR, VVF, VCT
Diameter····1.25mm
2
or more
4
Accidental malfunction of
abnormality-generated
controller.
1
Check transmission wave form or noise on
transmission wire.
2
Shut off the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSS-
NAY at the same time for two minutes or
more, and put the power on again. If mal-
function was accidental, the unit returns to
normal. If the same abnormality generates
again, controller of displayed address and
attribute may be defective.
4. Even controlling by the wireless
remote controller no beep is heard
and the unit does not start operat-
ing. Operation display is indicated
on wireless remote controller.
1
The pair number settings of the wireless remote
controller and indoor controller circuit board are mis-
matched.
1
Check the pair number settings.
OC338B-2.qxp 06.7.11 10:54 AM Page 37