75
(c) Capacity correction
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered com-
paring to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
1
1
Capacity curves for PUHZ-RP • HA model <Standard size>
2
2
Capacity curve for PUHZ-RP35, 50 models
<When gas pipe is one size smaller than standard size>
Cooling
Heating
100
95
90
85
80
75
70
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
Note: The permitted pipe length is up to 55m for RP35, 50, 60, 71 model.
Cooling RP71 model
Cooling RP35, 60 models
Cooling RP50, 100 models
Heating RP35, 50, 60,
71, 100, 125 and 140
models
(Up to 55m for RP35,
50, 60, 71 model)
Cooling RP125 model
Cooling RP140 model
Capacity ratio [%]
Corrected pipe length
5
10
15
20
25
30
35
40
45
50
55
80
Capacity ratio [%]
Corrected pipe length
85
90
95
100
Heating RP35, RP50
Cooling RP35
Cooling RP50
OCS01-3.qxp 05.5.16 10:09 AM Page 75
Summary of Contents for Mr.SLIM PUHZ-RP140YHA
Page 50: ...50 WIRED REMOTE CONTROLLER Unit mm 130 120 19 ...
Page 51: ...51 WIRELESS REMOTE CONTROLLER Unit mm 159 3 55 58 19 ...
Page 53: ...53 PEAD RP35EA PEAD RP50EA PEAD RP60EA PEAD RP71EA PEAD RP100EA PEAD RP125EA PEAD RP140EA ...
Page 54: ...54 PEAD RP60GA PEAD RP71GA PEAD RP100GA ...
Page 83: ...83 9 2 PLA RP AA 9 2 1 FRESH AIR INTAKE AMOUNT ...
Page 84: ...84 ...
Page 85: ...85 9 2 2 BRANCH DUCT Installation at site ...
Page 95: ...95 PEAD RP60GA PEAD RP71GA ...
Page 96: ...96 PEAD RP100GA ...
Page 103: ...103 ...