Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10
- 30
)
Thermistor (TH3)
<Outdoor Pipe>,
<Liquid>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<Outdoor 2-Phase Pipe>,
<2-Phase Pipe>
Thermistor (TH7)
<Outdoor>, <Ambient>
Thermistor (TH8)
<Heat Sink>
Thermistor (TH32)
<Comp.Surface>
Normal
160k
- 410k
4.3k
- 9.6k
39k
- 105k
TH4,TH32
TH3
TH6
TH7
TH8
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
)
Solenoid Valve Coil
<Four-Way Valve>
(21S4)
Motor for Compressor
(MC)
Linear Expansion Valve
(LEV-A)
Normal
Abnormal
Open or short
Except P125/P140VHA2
P125/P140VHA2
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20
)
Normal
Gray - Black
Gray - Red
Gray - Yellow
Gray - Orange
Abnormal
46 ± 3
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
)
Normal
1450 ± 150
Abnormal
Open or short
Solenoid Valve Coil
<Bypass valve>
(SV)
For P125, 140
Refer to next page.
Fan Motor (MF1,MF2)
1500 ± 150
1435 ± 150
P125/140V
P100V
0.88
P100Y
1.41
0.53
P125/140Y
1.02
Measure the resistance between the terminals with a tester.
(Winding temperature 20
)
Normal
Abnormal
Open or short
W
V
U
11-6. HOW TO CHECK THE PARTS