SW2 setting
Display detail
Explanation for display
Unit
45
:
Pipe temperature / Liquid (TH2) on error
occurring
-39 – 88
-39 – ~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When
−
15°C;
0.5 secs. 0.5secs. 2 secs.
Pressure saturation temperature (T
63HS
)
on error occurring
-39 – 88
-39 – 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When
−
15°C;
0.5 secs. 0.5secs. 2 secs.
Outdoor pipe temperature / 2-phase.
(TH6) on error occurring
-39 – 88
-39 – 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When
−
15°C;
0.5 secs. 0.5secs. 2 secs.
Outdoor outside temperature (TH7) on
error occurring
-39 – 88
-39 – 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When
−
15°C;
0.5 secs. 0.5secs. 2 secs.
Outdoor heatsink temperature (TH8) on
error occurring
-40 – 200
-40 – 200
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
15
15
15
:
:
:
:
:
0 – 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 secs. 0.5secs. 2 secs.
0 – 130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 secs. 0.5secs. 2 secs.
50
1
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
:
15
1
Discharge superheat on error occurring
SHd
0 – 255
Cooling = TH4-T
63HS
Heating = TH4-T
63HS
Sub cool on error occurring SC
0 – 130
Cooling = T
63HS
-TH3
Heating = T
63HS
-TH2
Thermo-on time until error stops
0 – 999
0 – 999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 secs. 0.5secs. 2 secs.
1
ON
2 3 4 5 6
Minute
15
4
The black square (
■
) indicates a switch position.
OCH534