16
[Procedure]
1. Press the CHECK button twice.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
ON/OFF
TEMP
FAN
VANE
MODE
CHECK LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK
display
Temperature
button
CHECK
button
Refrigerant
address
display
HOUR
button
ON/OFF
button
To be continued to the next page.
<
Malfunction-diagnosis method at maintenance service>
9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit-
tent buzzer sound, the operation lamp
blinks, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
Turn on the power.
Press the [CHECK] button twice.
Set address with [TEMP] button if system control is used.
Press the [ON/OFF] button to stop the self-check.
CHECK button
Address
TEMP. button
IC : Indoor unit
OC: Outdoor unit
Check code
Unit No.
Timer ON/OFF button
<To delete check code>
Display the error code on the self-check result display screen.
The address for self-check will blink when the
ON/OFF
button is pressed twice within 3 seconds.
– – – – : No trouble generated in the past.
F F F F : No corresponding unit.
■
IR wireless remote controller
■
Wired remote controller