OC246-50
DISASSEMBLY PROCEDURE
13
OPERATING PROCEDURE
PHOTOS&ILLUSTRATIONS
1. Removing the air intake grille
(1) Slide the knob of air intake grille to the direction of the
arrow
1
to open the air intake grille.
(2) Remove the string hook from the panel to pretend the
grille from dropping.
(3) Slide the shaft in the hinge to the direction of the arrow
2
and remove the air intake grille.
3. Removing the electrical box
(1) Disconnect the lead wire of the vane motor from the clamp,
and disconnect the white connector (10P).
(2) Remove the room temperature thermistor with the holder.
(3) Remove the bell mouth.(See photo 1)
(4) Disconnect the relay connector in the electrical box.
Red (3P) for fan motor
White (2P) for pipe temperature detecting thermistor
Blue (2P) for drain pump
White (3P) for drain sensor
(5) Remove the 3 screws from the electrical box, loosen anoth-
er 2 screws to remove the box.
<Electrical parts in the electrical box>
Indoor controller board
Power supply board
Terminal block
Capacitor
PL18AK
Be careful on removing heavy parts.
Photo 2
Figure 1
Air intake grille
Grille
Nut
Air intake grille knob
2. Removing the room temperature thermistor
(1) Remove the screw(
✕
1) in the room temperature thermistor
holder to remove the holder and the room temperature
thermistor.
(2) Remove the 1 screw from the bell mouth, and unscrew the
another 2 screws (fixed to the oval hole which has different
diameter) to remove the bell mouth.
(3) Hold the holder claw, and remove the room temperature
thermistor and holder.
(4) Disconnect the connector (red) in the indoor control board.
Bell mouth
Indoor controller board
Connector
Terminal
block
Photo 1
Screws
Room
temperature
thermistor
Air intake grille
Connector
Electrical
box
Power
supply
board
Turbo fan
Capacitor