![Mitsubishi Electric Mr.Slim PKFY-P32VGM Technical & Service Manual Download Page 11](http://html.mh-extra.com/html/mitsubishi-electric/mr-slim-pkfy-p32vgm/mr-slim-pkfy-p32vgm_technical-and-service-manual_1810220011.webp)
11
7
TROUBLE SHOOTING
7-1. How to check PKFY-P32VGM , PKFY-P40VGM , PKFY-P50VGM
Room temperature
thermistor (TH21)
Liquid pipe
thermistor (TH22)
Gas pipe thermistor
(TH23)
Trans
Vane motor
Fan motor
Linear expansion
valve
Disconnect the connector then measure the resistance with a tester.
(Surrounding temperature 10°C~30°C)
Disconnect the connector then measure the resistance with a tester.
Measure the resistance between the terminals with a tester.
(Surrounding temperature 20°C~30°C)
Disconnect the connector then measure the resistance with a tester.
(Surrounding temperature 20°C)
Normal
4.3k
'
~9.6k
'
Abnormal
Open or short
CNT(1)-(3)
CN3T(1)-(3)
Normal Abnormal
Open or short
Motor terminal or
relay connector
Normal
Abnormal
Red - Black
141.2
Ω
Open or short
White - Black
131.5
Ω
Normal
(1)-(5)
White-Red
150
Ω
±10%
Abnormal
Open or short
(2)-(6)
Yellow-Blown
(3)-(5)
Orange-Red
(4)-(6)
Blue-Brown
1
2
3
1
2
3
CNT
T
CN3T
Red
Blue
Blue
White
1
1
2
2
3
3
Red
White
Black
Relay connector
Protector
1
2
3
4
5
6
LEV
White
Yellow
Orange
Blue
Red
Brown
CN60
Parts name
Check method
Measure the resistance between the terminals with a tester.
(Surrounding temperature 20°C)
M
Blue
Brown
Yellow
Orange
Red
Pink
Normal
Abnormal
186
Ω
~ 214
Ω
Open or short
Red - Pink
Connector
Brown - Yellow
Brown - Blue
Red - Orange
About 70
Ω
About 1
Ω
OC179B