background image

5

4.1. Precautions

4.1.1. For devices that use R410A refrigerant

• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil

applied to the flared sections.

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the table to the below. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.

 Warning:

When installing or moving the air conditioner, use only the specified refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refriger-
ant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.

A24, A30, A36, A42

Liquid pipe

ø9.52 mm, 3/8 inch  thickness 0.8 mm, 1/32 inch

Gas pipe

ø15.88 mm, 5/8 inch  thickness 1.0 mm, 3/64 inch

• Do not use pipes thinner than those specified above.

4. Installing the refrigerant piping

4.2. Connecting pipes (Fig. 4-1)

• When commercially available copper pipes are used, wrap liquid and gas pipes

with commercially available insulation materials (heat-resistant to 100 °C, 212 °F or
more, thickness of 12 mm 1/2 inch or more).

• The indoor parts of the drain pipe should be wrapped with polyethylene foam insu-

lation materials (specific gravity of 0.03, thickness of 9 mm, 23/64 inch or more).

• Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening

flare nut.

• Use two wrenches to tighten piping connections.
• Use refrigerant piping insulation provided to insulate indoor unit connections. Insu-

late carefully.

A

Flare cutting dimensions

90

°

 

±

0.5

°

ø

A

R1/64 to R1/32

A

45

°±

2

°

B

C

D

Fig. 4-1

4.3. Insulating pipes (Fig. 4-2)

1. Slide the supplied pipe cover 

2

 over the gas tubing until it is pressed against the

sheet metal inside the unit.

2. Slide the provided pipe cover 

3

 over the liquid tubing until it is pressed against

the sheet metal inside the unit.

3. Tighten the pipe covers 

2

 and 

3

 at the both ends (15 - 20 mm, 5/8-3/4 inch) with

the supplied bands 

4

.

A

Gas tubing

E

Pipe cover 

3

B

Liquid tubing

F

Press the pipe cover against the sheet metal.

C

Band 

4

G

Refrigerant tubing heat insulating material

D

Pipe cover 

2

G

C

DE

A

B

D

E

F

C

Fig. 4-2

B

Flare nut tightening torque

C

Apply refrigerating machine oil over the entire flare seat surface.

D

Use correct flare nuts meeting the pipe size of the outdoor unit.

Available pipe size

A24, A30, A36, A42

Liquid side

ø9.52

Gas side

ø15.88

 : Factory flare nut attachment to the heat-exchanger.

Copper pipe O.D.

Flare dimensions

(mm, inch)

øA dimensions (mm, inch)

ø6.35, 1/4”

8.7 - 9.1, 11/32-23/64

ø9.52, 3/8”

12.8 - 13.2, 1/2-33/64

ø12.7, 1/2”

16.2 - 16.6, 41/64-21/32

ø15.88, 5/8”

19.3 - 19.7, 49/64-25/32

Copper pipe O.D.

Flare nut O.D.

Tightening torque

(mm, inch)

(mm, inch)

 (N·m, ft·lbs)

ø6.35, 1/4”

17, 43/64

14 - 18, 10-13

ø9.52, 3/8”

22, 7/8

34 - 42, 25-30

ø12.7, 1/2”

26, 1-3/64

49 - 61, 35-44

ø15.88, 5/8”

29, 1-9/64

68 - 82, 49-59

(inch)

 BG79U827H01_en

06.5.18, 10:13

5

Summary of Contents for Mr. SLIM PCA-A GA Series

Page 1: ...roughly before installing the air conditioner unit FOR INSTALLER Español MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad exterior antes de instalar la unidad de aire acondicionado PARA EL INSTALADOR BG79U827H01_cover 06 5 18 10 00 1 MITSUBISHI l ELECTRIC m Ir sl 11m ...

Page 2: ...can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre quency medical equipmen...

Page 3: ... 8 Wired remote controller 1 pc Fig 2 1 2 1 Outline dimensions Indoor unit Fig 2 1 Select a proper position allowing the following clearances for installation and mainte nance inch Models W D H A B C E A24 A30 1310 680 221 Min 270 Min 300 Min 500 Max 250 51 9 16 26 7 32 8 9 32 Min 10 5 8 Min 11 13 16 Min 19 11 16 Max 9 13 16 A36 A42 1310 680 281 Min 270 Min 300 Min 500 Max 250 51 9 16 26 7 32 10 5...

Page 4: ...rocedures 1 Install the washer 1 supplied with the unit and the nut to be locally procured 2 Set hook the unit through the suspending bolts 3 Tighten the nuts Check the unit installing condition Check that the unit is horizontal between the right and left sides Check that the unit slopes continuously downward from the front to the rear When embedding pipes into the wall 2 Installing the suspending...

Page 5: ...inch or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut Use two wrenches to tighten piping connections Use refrigerant piping insulation provided to insulate indoor unit connections Insu late carefully A Flare cutting dimensions 90 0 5 øA R 1 6 4 t o R 1 3 2 A 45 2 B C D Fig 4 1 4 3 Insulating pipes Fig 4 2 1 Slide the supplied pipe cover 2 ov...

Page 6: ...rvice entrance H Terminal block for power supply separate indoor outdoor unit power supplies K control application I Terminal block for indoor and outdoor units connection J Terminal block for remote controller K Grounding cable connector Fig 6 1 6 Electrical work A Drain pan B Drain tubing VP20 C Socket cover 6 D Joint socket 5 E Drain tubing cover 7 F Drain tubing sensor 5 Drainage piping work B...

Page 7: ...en S3 and S1 these terminals are not electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Use copper supply wires 3 Use wires rated 300V or more for the power supply cables and the indoor unit outdoor unit connecting cables 4 Install an earth longer than other cables Indoor unit model Indoor unit power supply Minim...

Page 8: ...ational code 2 Use copper supply wires 3 Use wires rated 300V or more for the power supply cables 4 Install an earth longer than other cables Indoor unit model Indoor unit power supply Minimum circuit ampacity Maximum rating of overcurrent protective device Indoor unit power supply Indoor unit power supply earth Indoor unit Outdoor unit 1 Indoor unit earth Remote controller Indoor unit 2 Indoor un...

Page 9: ...208 230 V DC12 V DC12 V DC12 V Circuit rating Wiring Wire No size For heat pump models 1 SW5 Set the DIP switch of the indoor unit control board SW5 1 ON SW5 2 3 OFF 2 3 1 SW5 Set the DIP switch of the indoor unit control board SW5 1 2 ON SW5 3 OFF 2 3 For cooling only models OFF ON SW5 1 A CONTROL K CONTROL SW5 2 heat pump models cooling only models SW5 3 MAIN SUB To change to K control set the D...

Page 10: ...CT blinks and Model No is lighted 2 Press the min button twice continuously Pair No 0 blinks 3 Press the temp button to set the pair number you want to set 4 Press the SET button with something sharp at the end Set pair number is lighted for three seconds then turned off D B 1 C A 2 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODELSELECT 2 4 3 A Fig 6...

Page 11: ...etting the unit number Press the temp button C and D to set the unit number 00 Direct the wire less remote controller toward the receiver of the indoor unit and press the min button B 3 Selecting a mode Enter 04 to change the power voltage setting using the C and D buttons Direct the wireless remote controller toward the receiver of the indoor unit and press the h button A Current setting number 1...

Page 12: ...e Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration proced...

Page 13: ...F Unit address 7 3 2 Wireless remote controller Fig 7 4 1 Turn on the power 2 Press the CHECK button twice Start this operation from the status of remote controller display turned off A CHECK begins to light B 00 begins to blink 3 While pointing the remote controller toward the unit s receiver press the h button The check code will be indicated by the number of times that the buzzer sounds from th...

Page 14: ...ways lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units only Indicates state of communication between the indoor and outdoor units Make sure that this LED is A control always blinking Ou...

Page 15: ...he op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Display A Press the MODE button to select the operation mode Press the FILTER button Waiting for stable operation Display D Stable operation 10 20 m...

Page 16: ...r o demasiado cerca de ella ya que los cambios de temperatura o el agua que gotea podrían dañarlos Cuando la humedad de la habitación supera el 80 o cuando el tubo de drenaje esté obstruido puede gotear agua de la unidad interior No instale la unidad interior en lugares donde el goteo pueda causar daños Si instala la unidad en un hospital o en un centro de comunicaciones recuer de que la unidad pr...

Page 17: ...ara la tubería del gas 3 Tapón de tubería 1 Tamaño pequeño para la tubería del líquido 4 Bandas 4 5 Adaptador de junta 1 marcado UNIT 6 Tapón para el adaptador 1 7 Tapón para la tubería 1 de drenaje 8 Controlador remoto cableado 1 Fig 2 1 1 2 3 4 5 6 7 Fig 3 1 Fig 3 2 Fig 3 3 E D H C W A B U N IT A C B 26 3 4 12 19 32 3 19 28 5 7 16 2 61 64 3 3 8 3 5 8 7 16 D E 1 13 16 F H D G E H G K J F 1 11 16 ...

Page 18: ...anche la unidad por medio de los pernos de suspensión 3 Apriete las tuercas Comprobación de las condiciones de instalación de la unidad Comprobar que la unidad haya quedado en posición horizontal de izquierda a dere cha Comprobar que la parte frontal ha quedado ligeramente más levantada que la par te posterior Empotrado de tubos en la pared 2 Instalación en el techo en primer lugar del soporte de ...

Page 19: ...ves de apriete para apretar las conexiones de los tubos Utilice el aislante de tubería de refrigerante suministrado para aislar las conexio nes de la unidad interior Realice los aislamientos con cuidado B Torsión de apriete de la tuerca abocardada Tubo de cobre O D Tuerca de abocardado Torsión de apriete mm inch O D mm inch N m ft lbs ø6 35 1 4 17 43 64 14 18 10 13 ø9 52 3 8 22 7 8 34 42 25 30 ø12...

Page 20: ...depósito de drenaje con 1 litro 1 4 gal aproximado de agua vertida desde la abertura de acceso del sensor del tubo 2 Compruebe el desagüe 3 Después de comprobar el correcto funcionamiento del drenaje volver a poner el tapón de la abertura de acceso del sensor del tubo A Depósito de drenaje B Tubo de drenaje VP20 C Tapón del adaptador 6 D Adaptador de junta 5 E Tapón del tubo de dre naje 7 F Sensor...

Page 21: ...os eléctricamente por el transformador u otro dispositivo Notas 1 El diámetro de los cables debe cumplir la normativa local y nacional 2 Utilice cables de cobre 3 Utilice cables con un régimen nominal de 300 V o superior para los cables de la fuente de alimentación y los cables de conexión de las unidades interior exterior 4 Instale un cable de toma de tierra más largo que el resto de los cables M...

Page 22: ...C12 V Conectores cuando la unidad se suministra de fábrica las conexiones están realizadas para alimentación de la unidad interior sumi nistrada desde la unidad exterior Alimentación de la unidad interior suministrada desde la unidad exterior cuando se suministra de fábrica Si las unidades interior y exterior presentan fuentes de alimentación independientes cambie las conexiones tal y como se mues...

Page 23: ... 2 AWG22 No polar AC 208 230 V DC12 V DC12 V DC12 V Los conmutadores DIP SW 5 2 y SW 5 3 sólo sur ten efecto cuando el conmutador DIP 5 1 K CON TROL está activado ON Cableado Cable n tamaño Rango del circuito 6 1 3 aplicación K control Están disponibles los siguientes patrones de conexión Los patrones de la fuente de alimentación de la unidad exterior varían en función del modelo Sistema 1 1 Coloq...

Page 24: ...porte del mando a distancia en el lugar deseado atornillándolo con tacos 2 Inserte la parte inferior del mando en el soporte A Mando a distancia B Pared C Pantalla del mando D Receptor La señal alcanza aproximadamente hasta 7 metros 23ft en línea recta con un ángulo de desviación de hasta 45 a la izquierda y la derecha de la línea central del receptor 3 Preparación inicial Fig 6 6 1 Introduzca las...

Page 25: ... botón TEMP C una vez para seleccionar 50 Apunte el mando a dis tancia hacia el receptor de la unidad interior y pulse el botón h A 2 Configuración del número de unidad Pulse el botónTEMP C y D para seleccionar el número de unidad 00 Apunte el mando a distancia hacia el receptor de la unidad interior y pulse el botón min B 3 Cómo seleccionar un modo Introduzca 04 para cambiar la tensión de aliment...

Page 26: ...nción No utilice el aire acondicionado si la resistencia de aislamiento es inferior a 1 0 MΩ Ω Ω Ω Ω Resistencia del aislamiento 7 2 Prueba de funcionamiento Están disponibles los siguientes 3 métodos 7 2 1 Al usar el controlador remoto cableado Fig 7 1 1 Encienda el aparato por lo menos 12 horas antes de llevar a cabo la prueba de funcionamiento 2 Pulse el botón de prueba de funcionamiento TEST P...

Page 27: ... 5 P5 Error de la bomba de drenaje 6 P6 Funcionamiento de seguridad por helada sobrecalentamiento 7 EE Error de comunicación entre unidades interior y exterior 8 P8 Error de temperatura del tubo 9 E4 Error de recepción de señal del controlador remoto 10 11 12 Fb Error del sistema de control de la unidad interior error de memoria etc Sin sonido No corresponde Controlador remoto inalámbrico Controla...

Page 28: ...o anteriormente No se acepta ninguna señal procedente del controlador remoto La luz OPE parpadea Se emite un pitido breve Si no se puede activar la unidad adecuadamente después de haberse llevado a cabo la ejecución de prueba consulte la tabla siguiente para suprimir la causa Síntoma Causa Controlador remoto cableado LED 1 2 tarjeta de circuito impreso en unidad exterior PLEASE WAIT PLEASE WAIT Có...

Page 29: ...l funcionamiento Si se detiene el aire acondicionado siga este pro cedimiento para que comience a funcionar COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Funcionamiento de refrigeración estable Funcionamiento de calefacción estable Cancelación de operación estable Pantalla A Pulse el botón MODE para elegir el modo de funcionamiento Pulse el botón FILTER Esperando funcionamiento estable Pant...

Page 30: ...îí 05 11 28 5 19 PM 1 ...

Page 31: ...îí 05 11 28 5 19 PM 1 ...

Page 32: ...to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U827H02 BG79U827H01_cover 06 5 18 10 00 2 J MITSUBISHI ELECTRIC CORPORATION ...

Reviews: