background image

7

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

3.  FLARING WORK AND PIPE CONNECTION

3-1. FLARING WORK

Pipe diameter  

[mm (inch)]

Nut 

(mm)

A [mm (inch)]

Tightening torque

Clutch type tool 

 

for R410A

Clutch type tool 

 

for R22

Wing nut type tool 

 

for R22

N•m

kgf•cm

ft·Ib

ø6.35  (1/4)

17

0 to 0.5

(0. to 0.02)

1.0 to 1.5

(0.04 to 0.06)

1.5 to 2.0

(0.06 to 0.08)

13.7 to 17.7

140 to 180

10 to 13

ø9.52  (3/8)

22

34.3 to 41.2

350 to 420

25 to 30

ø12.7  (1/2)

26

2.0 to 2.5

(0.08 to 1.0)

49.0 to 56.4

500 to 575

36 to 42

ø15.88  (5/8)

29

73.5 to 78.4

750 to 800

54 to 58

Tilted Uneven Burred

Good

No good

Burr

Copper pipe

Spare reamer

Pipe cutter

Smooth all 
around

Even length 
all around

Inside is shin-

ing without any 

scratches.

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

3-2. PIPE CONNECTION

•  Fasten flare nut with a torque wrench as specified in the table.

•  When fastened too tight, flare nut may brake after a long period and 

cause refrigerant leakage.

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the same 
manner applied for indoor unit.

•  For tightening, use a torque wrench or spanner and use the same 

tightening torque applied for indoor unit.

3-3. INSULATION AND TAPING

1) Cover piping joints with pipe cover.

2) For outdoor unit side, surely insulate every piping including valves.

3) Using piping tape (E), apply taping starting from the entry of outdoor 

unit.

•  Stop the end of piping tape (E) with tape (with adhesive agent at

-

tached).

•  When piping have to be arranged through above ceiling, closet or 

where the temperature and humidity are high, wind additional com

-

mercially sold insulation to prevent condensation.

Copper 
pipe

1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)

2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3)

•  Put the end of the copper pipe to downward direction as you 

remove burrs in order to avoid to let burrs drop in the piping.

3) Remove flare nuts attached to indoor and outdoor units, then put them 

on pipe having completed burr removal. (Not possible to put them on 

after flaring work.) 

4) Flaring  work  (Fig.  4,  5).  Firmly  hold  copper  pipe  in  the  dimension 

shown  in  the  table.  Select  A  mm  from  the  table  according  to  the  tool 

you use.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared section and do 

flaring work again.

SG79Y871H02.indb   7

9/7/2007   1:09:41 PM

Summary of Contents for Mr. Slim MXZ-3A30NA

Page 1: ...door unit for indoor unit in stallation Español ATTENTION This manual mentions how to install only the outdoor unit MXZ 3A30NA MXZ 4A36NA As for the way of installation for indoor unit MSZ A09NA MSZ A12NA MSZ A15NA MSZ A17NA and MSZ A24NA please refer to the installation manual being attached each indoor unit The installation manual details the suggested installation method Any structural alterati...

Page 2: ...e harmful gas could be gener ated n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate ...

Page 3: ...and or some baffle boards Note It is advisable to make a piping loop near outdoor unit so as to reduce vibration transmitted from there Note When operating the air conditioner in low outside temperature be sure to follow the instructions described below Never install the outdoor unit in a place where its air inlet outlet side may be exposed directly to wind To prevent exposure to wind install the ...

Page 4: ...ole cover 1 E Piping tape 1 F Extension drain hose or soft PVC hose 15 mm 19 32 in inner dia or hard PVC pipe VP16 1 G Refrigeration oil Little amount H Putty 1 I Pipe fixing band 2 to 7 J Fixing screw for I 2 to 7 K Wall hole sleeve 1 L Soft PVC hose 25 mm 31 32 in inner dia or hard PVC pipe VP25 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m 39 4 in away ...

Page 5: ... MSZ A17NA MSZ A24NA Power supply V PHASE Hz 208 230 1 60 Min Circuit Ampacity A 1 0 1 0 1 0 1 0 1 0 Fan motor F L A 0 76 0 76 0 76 0 76 0 76 OUTDOOR UNIT MXZ 3A30NA MXZ 4A36NA Power supply V PHASE Hz 208 230 1 60 Max Fuse size time delay A 20 20 Min Circuit Ampacity A 15 19 Fan motor F L A 0 93 0 93 Compressor R L A 11 14 4 L R A 15 15 Control voltage Indoor unit Remote controller Wireless Indoor...

Page 6: ...ct wires to the matching numbers of terminals CONNECTING WIRES AND CONNECTING GROUND WIRE Use solid conductor AWG14 or stranded conductor AWG18 AWG16 or AWG14 Use double insulated copper wire with 300 V insulation Use copper conductors only Follow local electrical code POWER SUPPLY CABLE AND GROUND WIRE Use solid or stranded conductor AWG14 Use copper conductors only Follow local electrical code W...

Page 7: ...r tightening use a torque wrench or spanner and use the same tightening torque applied for indoor unit 3 3 INSULATION AND TAPING 1 Cover piping joints with pipe cover 2 For outdoor unit side surely insulate every piping including valves 3 Using piping tape E apply taping starting from the entry of outdoor unit Stop the end of piping tape E with tape with adhesive agent at tached When piping have t...

Page 8: ...to 5 turns Stop valve for LIQUID 4 PURGING PROCEDURES LEAK TEST AND TEST RUN Pressure gauge for R410A Precautions when using the control valve When attaching the control valve to the service port valve core may de form or loosen if excess pressure is applied This may cause gas leak Service port Charge hose for R410A Body Close Open Control valve A When attaching the control valve to the service po...

Page 9: ...roller holder how to clean precautions for operation etc Recommend the user to read the OPERATING INSTRUCTIONS care fully LED indication during detection LED 1 Red 2 Yellow 3 Green Lighted Lighted Blinking Result of piping wiring correction function LED Result 1 Red 2 Yellow 3 Green Lighted Not lighted Lighted Completed Corrected successfully Blinking Blinking Blinking Cannot be corrected Other in...

Page 10: ...10 ...

Page 11: ...s consulte el manual de instala ción incluido en cada unidad interior Español ATENCIÓN Este manual corresponde únicamente a la instalación de la unidad exterior MXZ 3A30NA MXZ 4A36NA Para la instalación de las unidades interiores MSZ A09NA MSZ A12NA MSZ A15NA MSZ A17NA y MSZ A24NA consulte el manual de ins talación que se incluye en cada unidad interior El manual de instalación detalla el método d...

Page 12: ...frigerante Si se produjeran pérdidas de gas refrigerante en un interior y entraran en contacto con la llama de un calefactor con ventilador un calentador una estufa etc se generarían sustancias nocivas n Utilice las herramientas apropiadas y los materiales de conducción adecuados para la instalación La presión del refrigerante R410A es 1 6 veces mayor que la del R22 Si no se utilizan herramientas ...

Page 13: ...Instale la unidad en horizontal Instálela en un área donde no sufra el efecto provocado por una neva da viento o nieve En zonas de intensa nieve le rogamos que instale un toldo pedestal y o algunas pantallas acústicas planas Nota Se recomienda establecer el circuito cerrado de la tubería cerca de la unidad exterior para reducir la vibración que pudiera transmitirse desde ese punto Nota Si utiliza ...

Page 14: ...tubería de PVC blando de 15 mm 19 32 pulg en el interior o tubería VP16 de PVC duro 1 G Aceite refrigerante Poca cantidad H Masilla 1 I Banda de fijación del tubo 2 a 7 J Tornillo de fijación para I 2 a 7 K Manguito del orificio de la pared 1 L Tubería de PVC blando de 25 mm 31 32 pulg en el interior o tubería VP25 de PVC duro 1 Nota Tienda el cable de conexión de la unidad interior exterior B y e...

Page 15: ... MSZ A12NA MSZ A15NA MSZ A17NA MSZ A24NA Alimentación V FASE Hz 208 230 1 60 Amperaje mín del circuito A 1 0 1 0 1 0 1 0 1 0 Motor del ventilador F L A 0 76 0 76 0 76 0 76 0 76 UNIDAD EXTERIOR MXZ 3A30NA MXZ 4A36NA Alimentación V FASE Hz 208 230 1 60 Tamaño máx fusible retardo A 20 20 Amperaje mín del circuito A 15 19 Motor del ventilador F L A 0 93 0 93 Compresor R L A 11 14 4 L R A 15 15 Tensión...

Page 16: ...xión Interruptor de desconexión Conecte los cables al número correspondiente de terminales CONEXIÓN DE CABLES Y CONEXIÓN DEL CABLE DE TIERRA Use un conductor sólido AWG14 o un conductor trenzado AWG18 AWG16 o AWG14 Use un cable con aislamiento doble aislamiento de 300 V Use únicamente conductores de cobre Siga la normativa eléctrica local CABLE DE ALIMENTACIÓN Y CABLE DE TIERRA Utilice un conducto...

Page 17: ... dinamométrica o una llave de tuercas y utilice el mismo par de torsión aplicado en la unidad interior 3 3 AISLAMIENTO TÉRMICO Y FORRADO CON CINTA 1 Cubra las uniones de tuberías con cubiertas de tubería 2 En el lado de la unidad exterior aísle bien cada una de las tuberías y válvulas 3 Aplique cinta de tuberías E a partir de la entrada de la unidad exterior Sujete con cinta adhesiva el extremo de...

Page 18: ...AS Y FUNCIONAMIENTO DE PRUEBA Manómetro para R410A Precauciones al utilizar la válvula de control Al conectar la válvula de control al puerto de servicio la pieza interior de la válvula podría deformarse o soltarse si se aplica demasiada presión Esto podría provocar fugas de gas Puerto de servicio Manguera de car ga para R410A Cuerpo Cerrado Abierta Válvula de control A Al conectar la válvula de c...

Page 19: ...olador remoto cómo limpiar precauciones para el funcionamiento etc Aconseje al usuario que lea atentamente el MANUAL DE INSTRUC CIONES Indicadores luminosos durante la detección Indicador 1 rojo 2 amarillo 3 verde Iluminado Iluminado Parpadea Resultado de la función de corrección de tuberías conexiones Indicador Resultado 1 rojo 2 amarillo 3 verde Iluminado No ilumina do Iluminado Finalizado corre...

Page 20: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JG79A073H01 ...

Reviews: