47
3. Outdoor unit failure mode table
OPERATION
INDICATOR
upper lamp
(Indoor unit)
Abnormal point
(Failure mode / protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/
outdoor unit
failure mode
recall function
Outdoor unit
failure mode
recall function
OFF None
(Normal)
—
—
—
—
—
2-time
fl
ash
2.5 seconds
OFF
Outdoor power system
—
Overcurrent protection cut-out operates
3 consecutive times within 1 minute
after the compressor gets started.
Reconnect connectors.
Refer to 10-5. "How
to check inverter/
compressor".
Check stop valve.
•
•
•
○
○
3-time
fl
ash
2.5 seconds
OFF
Discharge temperature
thermistor
1-time
fl
ash every
2.5 seconds
Thermistor shorts or opens during
compressor running.
Refer to 10-5. "Check
of outdoor thermistors".
Defective outdoor
thermistors can be
identi
fi
ed by checking
the blinking pattern of
LED.
•
○
○
Defrost thermistor
(MUZ)
Fin temperature thermistor
3-time
fl
ash
2.5 seconds OFF
P.C. board temperature
thermistor
4-time
fl
ash
2.5 seconds OFF
Ambient temperature
thermistor
2-time
fl
ash
2.5 seconds OFF
Outdoor heat exchanger
temperature thermistor
(MUZ-GE24, MUY-GE24)
4-time
fl
ash
2.5 seconds
OFF
Overcurrent 11-time
fl
ash
2.5 seconds OFF
Large current
fl
ows into intelligent
power module/ power module 1.
Reconnect compressor
connector.
Refer to 10-5. "How
to check inverter/
compressor".
Check stop valve.
•
•
•
—
○
Compressor synchronous
abnormality (Compressor start-
up failure protection)
12-time
fl
ash
2.5 seconds OFF
Waveform of compressor current is
distorted.
Reconnect compressor
connector.
Refer to 10-5. "How
to check inverter/
compressor".
•
•
—
○
5-time
fl
ash
2.5 seconds
OFF
Discharge temperature
—
Temperature of discharge temperature
thermistor exceeds 241°F (116°C),
compressor stops.
Compressor can restart if discharge
temperature thermistor reads 212°F
(100°C) or less 3 minutes later.
Check refrigerant
circuit and refrigerant
amount.
Refer to 10-5. "Check
of LEV".
•
•
—
○
6-time
fl
ash
2.5 seconds
OFF
High pressure
—
Temperature of indoor coil thermistor
exceeds 158°F (70°C) in HEAT mode
(MUZ only).
Temperature of outdoor
heat exchanger temperature thermistor
exceeds 158°F (70°C) in COOL mode.
Check refrigerant
circuit and refrigerant
amount.
Check stop valve.
•
•
—
○
7-time
fl
ash
2.5 seconds
OFF
Fin temperature/ P.C. board
temperature
7-time
fl
ash
2.5 seconds OFF
Temperature of
fi
n temperature
thermistor on the inverter P.C. board
exceeds 167 ~ 176°F (75 ~ 80°C), or
temperature of P.C. board temperature
thermistor on the inverter P.C. board
exceeds 158 ~ 167°F (70 ~ 75°C).
Check around outdoor
unit.
Check outdoor unit air
passage.
Refer to 10-5. "Check
of outdoor fan motor".
•
•
•
—
○
8-time
fl
ash
2.5 seconds
OFF
Outdoor fan motor
—
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor fan
start-up.
Refer to 10-5. "Check
of outdoor fan motor".
Refer to 10-5. "Check
of inverter P.C. board".
•
—
○
9-time
fl
ash
2.5 seconds
OFF
Nonvolatile memory data
5-time
fl
ash
2.5 seconds OFF
Nonvolatile memory data cannot be
read properly.
Replace the inverter
P.C. board.
•
○
○
Power module
(MUZ-GE24, MUY-GE24)
6-time
fl
ash
2.5 seconds OFF
The interphase short circuit occurs
in the output of the intelligent power
module (IPM)/power module (IPM) 1.
The compressor winding shorts circuit.
Refer to 10-5. "How
to check inverter/
compressor".
•
10-time
fl
ash
2.5 seconds
OFF
Discharge temperature
—
Temperature of discharge temperature
thermistor has been 122°F (50°C) or
less for 20 minutes.
Refer to 10-5. "Check
of LEV".
Check refrigerant
circuit and refrigerant
amount.
•
•
—
○
NOTE
: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).
1
Intelligent power module:
MUZ-GE09/12/15/18/24NA
,
MUY-GE09/12/15/18/24NA
Power module:
Other models
OBH549F
Summary of Contents for Mr. Slim MUZ-GE15NA-1
Page 13: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549F ...
Page 14: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549F ...
Page 15: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549F ...
Page 16: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549F ...
Page 17: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549F ...
Page 18: ...18 MUY GE15NA MUZ GE15NAH2 OBH549F ...
Page 19: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549F ...
Page 20: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549F ...
Page 21: ...21 MUZ GE18NAH MUY GE18NA OBH549F ...
Page 22: ...22 MUY GE18NA 1 OBH549F ...
Page 23: ...23 MUZ GE24NA OBH549F ...
Page 24: ...24 MUY GE24NA OBH549F ...
Page 73: ...73 OBH549F ...