152
1 SERVO PARAMETER DETAILS
1.8 Motor extension setting servo parameters group ([Pr. PL_ _ ])
[Pr. PL08_Function selection L-3 (*LIT3)]
Select a function of the linear servo motor or direct drive motor.
[Pr. PL08.0_Magnetic pole detection method selection]
0: Position detection method
4: Minute position detection method
If detecting magnetic poles in a vertical axis, configure a system with equipment such as a counterweight to prevent the linear
servo motor from moving with the force of gravity.
[Pr. PL08.2_Magnetic pole detection - Stroke limit enabled/disabled selection]
0: Enabled
1: Disabled
[Pr. PL09_Magnetic pole detection voltage level (LPWM)]
Set a direct current exciting voltage level in the magnetic pole detection.
If [AL. 032 Overcurrent], [AL. 050 Overload 1], or [AL. 051 Overload 2] occurs during the magnetic pole detection, set a
smaller value.
If [AL. 027 Initial magnetic pole detection error] occurs during the magnetic pole detection, set a larger value.
Initial value
Setting range
Setting method
Ver.
00001010h
Refer to the relevant detail No.
Each axis
Refer to the relevant detail No.
Initial value
Setting range
Ver.
0h
Refer to the text
A0
Initial value
Setting range
Ver.
0h
Refer to the text
A0
Initial value
Setting range
Setting method
Ver.
30 [%]
0 to 100
Each axis
A0