background image

EN-9

3.  OUTDOOR UNIT INSTALLATION

3-4. INSULATION AND TAPING

1) Cover piping joints with pipe cover.

2) For outdoor unit side, surely insulate every piping including valves.

3) Using piping tape (G), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (G) with tape (with adhesive agent attached).

•  When piping have to be arranged through above ceiling, closet or where the tempera

-

ture and humidity are high, wind additional commercially sold insulation to prevent 

condensation.

3-2. FLARING WORK

1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)

2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3)

•  Put the end of the copper pipe to downward direction as you remove burrs in order 

to avoid to let burrs drop in the piping.

3) Remove flare nuts attached to indoor and outdoor units, then put them on pipe having 

completed burr removal. (Not possible to put them on after flaring work.) 

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. 

Select A mm from the table according to the tool you use.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared section and do flaring work again.

3-3. PIPE CONNECTION

•  Fasten flare nut with a torque wrench as specified in the table.

•  When fastened too tight, flare nut may break after a long period and cause refrigerant 

leakage.

•  Be sure to wrap insulation around the piping. Direct contact with the bare piping may 

result in burns or frostbite.

Indoor unit connection

Connect both liquid and gas pipings to indoor unit.

•  Apply a thin coat of refrigeration oil (K) on the flared ends of the pipes. Do not apply 

refrigeration oil on screw threads. Excessive tightening torque will result in damage 

on the screw.

•  For connection, first align the center, then tighten the first 3 to 4 turns of flare nut.

•  Use tightening torque table above as a guideline for indoor unit side union joint section, 

and tighten using two wrenches. Excessive tightening damages the flare section.

Copper 

pipe

Good

Tilted Uneven Burred

No good

Fig. 1

Fig. 2

Burr

Copper pipe

Spare reamer

Pipe cutter

Clutch type

Flaring tool

Fig. 4

Fig. 3

Smooth all 

around

Even length 

all around

Inside is shining 

without any 

scratches.

Flare nut

Die

Fig. 5

Fig. 6

Copper 

pipe

Wing nut type

 WARNING

When installing the unit, securely 

connect the refrigerant pipes be-

fore starting the compressor.

 WARNING

Reusable mechanical connectors and flared joints are not al-

lowed indoors.

When connecting the refrigerant piping by brazing, rather than 

using flare connections, complete all brazing prior to connecting 

indoor unit to outdoor unit.

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch 

type tool 

for R32, 

R410A

Clutch 

type tool 

for R22

Wing nut 

type tool 

for R22

N•m

kgf•cm

ø6.35 (1/4”)

17

0 to 0.5

1.0 to 1.5

1.5 to 2.0

13.7 to 17.7 140 to 180

ø9.52 (3/8”)

22

34.3 to 41.2 350 to 420

ø12.7 (1/2”)

26

2.0 to 2.5

49.0 to 56.4 500 to 575

ø15.88 (5/8”)

29

73.5 to 78.4 750 to 800

3-1. CONNECTING WIRES FOR OUTDOOR UNIT

1) Open the service panel.

2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from the 

indoor unit correctly on the terminal block. Be careful not to make mis-wiring. Fix the wire 

to the terminal block securely so that no part of its core is appeared, and no external 

force is conveyed to the connecting section of the terminal block. 

3) Firmly tighten the terminal screws to prevent them from loosening. After tightening, pull 

the wires lightly to confirm that they do not move.

4) Connect power supply cord (K).

5) Fix indoor/outdoor unit connecting wire (A) and power supply cord (K) with the cord 

clamp.

6) Close the service panel securely.

•  Make earth wire a little longer than others. (More than 100 mm)

•  For future servicing, give extra length to the connecting wires.

•  Be sure to attach each screw to its correspondent terminal when securing the cord 

and/or the wire to the terminal block.

35 mm

15 mm

Lead wire

Power supply cord (K)

Terminal block

Cord clamp

Cord clamp

Power supply 

cord (K)

Terminal block

Indoor/outdoor 

unit connect

-

ing wire (A)

Always fix the power supply 

cord on this side.

<KW25, 35, 42>

<KW50(HZ), 60(HZ)>

RH79A056H01_4th.indd   9

2020/08/19   12:50:23

Summary of Contents for MFZ-KW25VG

Page 1: ...FLOOR TYPE AIR CONDITIONERS REFRIGERANT R32 English INSTALLATION MANUAL For INSTALLER MFZ KW25VG MFZ KW35VG MFZ KW42VG MFZ KW50VG MFZ KW60VG RH79A056H01_4th indd 1 2020 08 19 12 50 18 ...

Page 2: ...nstalling relocating or servicing the unit make sure that no substance other than the specified refrigerant R32 enters the refrigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explo sion or injury The use of any refrigerant other than that specified for the system will cause mechanical failure system malfunction or unit breakdown In t...

Page 3: ...asy to operate and easily visible Where children cannot touch it Select a position about 1 2 m above the floor and check that signals from the remote controller are surely received by the indoor unit from that position beep or beep beep receiving tone sounds After that attach remote controller holder to a pillar or wall and install wireless remote controller Note In rooms where inverter type fluor...

Page 4: ...foam plastic 0 045 specific gravity 9 Be sure to use the insulation of specified thickness Excessive thickness may cause incorrect installation of the indoor unit and insufficient thickness may cause dew drippage KW25 35 42 KW50 60 Pipe length and height difference Max pipe length 20 30 m Max height difference 12 15 m Max number of bends 5 6 10 Refrigerant adjustment A 7 20 g m Insulation thicknes...

Page 5: ...t and sides of unit are clear 2 When any 2 sides of left right and rear of unit are clear 3 The manufacturing year and month is indicated on the spec name plate clear 1 KW25 35 42 KW50 60 Appearance of the out door unit may differ from some models Air inlet Air outlet 2 10 mm 21 mm slot 800 840 mm 150 175 mm 500 mm 344 5 390 mm 285 330 mm 304 325 349 371 mm 40 mm Air inlet 350 mm or more Indoor un...

Page 6: ...lowing figure is a view of the bottom of the indoor unit from above FOR REAR OR LEFT REAR PIPING The following figure is a front view of the indoor unit installation location FOR LEFT PIPING FOR RIGHT PIPING HOLE POSITIONS ø65 mm KW25 35 42 ø75 ø80 mm KW50 60 5 7 mm 2 3 INDOOR UNIT PREPARATION Remove the front panel of the indoor unit 1 Push down the tab on the both sides of the unit to open the f...

Page 7: ...wire or cram it into small space Take caution not to damage the wires Be sure to attach each screw to its correspondent terminal when securing the cord and or the wire to the terminal block 2 5 CONNECTING WIRES FOR INDOOR UNIT 1 Remove VA clamp 2 Pass indoor outdoor unit connecting wire A from the back of the indoor unit and process the end of the wire 3 Loosen terminal screw and connect first the...

Page 8: ...d point downward for easy drain flow Fig 1 If the drain hose provided with the indoor unit is too short connect it with drain hose J that should be provided at your site Fig 2 When connecting the drain hose to the hard vinyl chloride pipe be sure to insert it securely into the pipe Fig 3 Wrap the felt tape 11 tightly around the pipes and hose starting near where the pipes and hose are routed from ...

Page 9: ...necting cable should be stored and placed where customers cannot touch it Rear horizontal vane 2 9 HOW TO ATTACH THE LABEL AND THE EXPLANATION The breaker must be always ON except when performing maintenance or inspection Hang the accompanying label 14 or 15 on the breaker and explain it to customers When turning the breaker OFF the power is not supplied to the refrigerant sensor mounted in the in...

Page 10: ...damages the flare section Copper pipe Good Tilted Uneven Burred No good Fig 1 Fig 2 Burr Copper pipe Spare reamer Pipe cutter Clutch type Flaring tool Fig 4 Fig 3 Smooth all around Even length all around Inside is shining without any scratches Flare nut Die Fig 5 Fig 6 Copper pipe Wing nut type WARNING When installing the unit securely connect the refrigerant pipes be fore starting the compressor ...

Page 11: ... the indoor outdoor unit connecting wire A for mis wiring After the test run emergency mode set temperature 24ºC will start 2 To stop operation press the E O SW several times until all LED lamps turn off Refer to operating instructions for details Checking the remote infrared signal reception Press the ON OFF button on the remote controller 12 and check that an electronic sound is heard from the i...

Page 12: ...E TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment RH79A056H01_cover_1st indd 1 2020 08 19 12 51 21 ...

Reviews: