![Mitsubishi Electric MEsoftstart/I00 Users, Installation & Instruction Manual Download Page 26](http://html.mh-extra.com/html/mitsubishi-electric/mesoftstart-i00/mesoftstart-i00_users-installation-and-instruction-manual_1811805026.webp)
26 Installation Instructions
Cooling system types for soft starter cabinet
The heat that the soft starter and other equipment (transformers, lamps, resistors, etc.) generates, as well as any incoming
heat (such as direct sunlight) must be dissipated to keep the temperature inside the cabinet lower than the permissible
operating temperature of the soft starter.
When selecting or designing a cabinet for the soft starter, the following cooling considerations (for the cabinet) must be
considered:
The cooling systems are classified as follows in terms of the cooling calculation method.
(a) Cooling by natural heat dissipation from the cabinet surface (totally enclosed type).
(b) Cooling by heatsink (e.g. aluminium fin).
(c) Cooling by ventilation (forced ventilation type, pipe ventilation type).
(d) Cooling by heat exchanger or cooler (e.g. heat pipe, cooler).
Table 9: Cooling systems for soft starter cabinet
Cooling system
Cabinet layout
Comment
Natural
cooling
Natural ventilation
(enclosed, open type)
This system is low in cost and generally used, but the cabinet size
increases as the soft starter capacity increases.This system is for relatively
small capacities.
Natural ventilation
(totally enclosed type)
Being a totally enclosed type, this system is the most appropriate for
hostile environment having dust, dirt, oil mist, etc. The cabinet size
increases depending on the soft starter capacity.
Forced
cooling
Heatsink cooling
This system has restrictions on the heatsink mounting position and area.
This system is for relatively small capacities.
Forced ventilation
This system is for general indoor installation. This is appropriate for
cabinet downsizing and cost reduction and often used.
Heat pipe
This is a totally enclosed for cabinet downsizing
Summary of Contents for MEsoftstart/I00
Page 15: ...15 Introduction Figure 3 Soft starter terminal and component identification ...
Page 37: ...37 Wiring Figure 23 Fitting protective guards over terminals ...
Page 77: ...77 Basic operation Pro models Figure 40 Understanding the data display ...
Page 97: ...97 MEsoftstart PC Interface Application Figure 60 MEsoftstart PC Application Fault screen ...
Page 119: ......