7 APPLICATION INSTRUCTIONS
7.7 Debugging and Failure Diagnostic Instructions
629
7
Generating a continuation error
PALERT(P)
This instruction generates a continuation error in the CPU module.
■
Execution condition
Setting data
■
Description, range, data type
■
Applicable devices
Processing details
• This instruction generates a continuation error (error code: 1810H) in the CPU module. When the instruction is executed,
SM0 turns on and the ERROR LED of the CPU module turns on. SM1 does not turn on.
• Data (16-bit signed binary) specified by (s) is stored in the detailed information 2 of the error code 1810H.
• The PALERT(P) instruction is useful for debugging since a continuation error can be simulated at the start-
up of the system. The instruction execution point can be identified by checking the detailed information 2 of
the error code 1810H.
Operation error
There is no operation error, except the error (error code: 1810H) which occurs by executing the PALERT(P) instruction.
Ladder
ST
ENO:=PALERT(EN,s);
ENO:=PALERTP(EN,s);
FBD/LD
Instruction
Execution condition
PALERT
PALERTP
Operand
Description
Range
Data type
Data type (label)
(s)
Data to be stored in the detailed information 2 of the error
code 1810H or device number where the data is stored
-32768 to 32767
16-bit signed binary
ANY16
EN
Execution condition
Bit
BOOL
ENO
Execution result
Bit
BOOL
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z
LT, LST,
LC
LZ
K, H E
$
(s)
RnCPU RnENCPU
RnSFCPU RnSFCPU
RnPCPU
RnPCPU
(Standard)
(Safety)
(Redundant)
(Process)
(s)
EN
ENO
s
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......