1908
27 ARITHMETIC OPERATION FUNCTIONS
27.2 Multiplication
27.2
Multiplication
MUL(_E)
These functions output the product of input values ((s1)
(s2)
(s28)).
*1 The input variable s can be changed within the range from 2 to 28.
Setting data
■
Description, type, data type
Processing details
■
Operation processing
• These functions multiply the INT, DINT, REAL, or LREAL data type values input to (s1) to (s28) ((s1)
(s2)
(s28)), and
output the operation result, in the same data type as (s), from (d).
Ex.
Data type: INT
• Input an INT, DINT, REAL, or LREAL data type value to (s1) to (s28).
• If an underflow or overflow occurs in the operation result, the output from (d) will be as follows.
Ladder, FBD/LD
Structured text
[Without EN/ENO]
[With EN/ENO]
[Without EN/ENO]
d:=MUL(s1,s2);
[With EN/ENO]
d:=MUL_E(EN,ENO,s1,s2);
Argument
Description
Type
Data type
EN
Execution condition (TRUE: Executed, FALSE: Not executed)
Input variable
BOOL
s1 (IN1) to s28 (IN28)
Input
Input variable
ANY_NUM
ENO
Output status (TRUE: Normal, FALSE: Abnormal)
Output variable
BOOL
d
Output
Output variable
ANY_NUM
Data type: INT
Data type: DINT
Data type: REAL/LREAL
• Even if an underflow or overflow occurs, no
operation error is issued. When MUL_E is used,
ENO outputs TRUE.
• Even if the operation result is outside the INT data
type range, the INT data type value is output; (In
this case, the output value is of INT data type with
the upper 16 bits deleted although the operation
result is a DINT data type value.)
• If the operation result is outside the INT data type
range, convert the input value to the DINT data
type by using the INT_TO_DINT function, and
then perform operation.
• Even if an underflow or overflow occurs, no
operation error is issued. When MUL_E is used,
ENO outputs TRUE.
• Even if the operation result is outside the DINT
data type range, the DINT data type value is
output; (In this case, the output value is of DINT
data type with the upper 32 bits deleted although
the operation result is 64-bit data.)
• If the operation result is outside the DINT data
type range, convert the input value to the REAL
data type by using the DINT_TO_REAL function,
and then perform operation.
An operation error occurs and an undefined value
is output.
RnCPU RnENCPU
RnSFCPU RnSFCPU
RnPCPU
RnPCPU
(Standard)
(Safety)
(Redundant)
(Process)
s1
d
s2
EN
ENO
d
s1
s2
(s1)
(s2)
(d)
1500
15
×
100
INT
INT
INT
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......