688
39 PRECAUTIONS ON PROGRAMMING
39.1 Instructions Not Available in System Using SIL2 Process CPU
Instructions whose operations vary depending on tracking of the
signal flow memory
This section describes the instructions whose operations after the system switching vary depending on whether the signal
flow memory is tracked or not. The operations vary when one of the following instructions is executed among program
organization units that have the signal flow memory, to which tracking can be performed.
Rising instruction
If the system switching is performed without the signal flow memory being tracked, the signal flow memory of the new control
system turns on. Thus, a rising instruction whose execution condition turned on during system switching will not be executed.
Falling instruction
If the system switching is performed without the signal flow memory being tracked, the signal flow memory of the new control
system turns on. Thus, a falling instruction whose execution condition turned off before the system switching will be executed.
SCJ instruction
■
When the signal flow memory is not tracked
Once the system switching is performed, the execution condition of the SCJ instruction turns on after the signal flow memory
of the new control system turns off. In the new control system, processing jumps to the pointer specified by the SCJ instruction
in the first scan.
Classification/type of special relay
Instruction symbol
Rising instruction
LDP, ANDP, ORP, LDPI, ANDPI, ORPI, PLS, MEP, EGP, SET F, RST F, FF,
LEDR, DUTY, LOGTRG, LOGTRGR,
P (including MOVP and INCP), SP.
,
JP.
, GP.
, ZP.
Falling instruction
LDF, ANDF, ORF, LDFI, ANDFI, ORFI, PLF, MEF, EGF
SCJ instruction
SCJ
Data processing instructions
SORTD(_U), DSORTD(_U)
TIMCHK instruction
TIMCHK
XCALL instruction
XCALL
Rising instruction using SM1643 as an execution condition
(1) After system switching, the processing jumps in the first and later scans.
ON
OFF
(1)
Execution condition of the SCJ
instruction
Jump by using the SCJ instruction
(old control system)
Jump by using the SCJ instruction
(new control system)
Jump
No jump
Jump
No jump
System switching start
System switching completion
Systems are being switched.
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......