8 APPLICATION INSTRUCTION
8.12 Data Control Instruction
567
8
Scaling 32-bit binary data (point coordinates)
DSCL(P)(_U)
These instructions process the scaling conversion data (in 32-bit data units) specified by (s2) by scaling it based on the input
value specified by (s1), and store the operation result in the device specified by (d).
Setting data
■
Descriptions, ranges, and data types
*1 The numbers of coordinate points of (s2)+1 and (s2) are 32-bit unsigned binary data.
■
Applicable devices
Ladder diagram
Structured text
ENO:=DSCL(EN,s1,s2,d);
ENO:=DSCLP(EN,s1,s2,d);
ENO:=DSCL_U(EN,s1,s2,d);
ENO:=DSCLP_U(EN,s1,s2,d);
FBD/LD
Operand
Description
Range
Data type
Data type (label)
(s1)
DSCL(P)
Input value used in scaling or head device
number storing the input value
-2147483648 to +2147483647
32-bit signed binary
ANY32_S
DSCL(P)_U
0 to 4294967295
32-bit unsigned binary
ANY32_U
(s2)
DSCL(P)
Head device number where the scaling
conversion data is stored
32-bit signed binary
ANY32_S
DSCL(P)_U
32-bit unsigned binary
ANY32_U
(d)
DSCL(P)
Head device number storing the output value
controlled by scaling
32-bit signed binary
ANY32_S
DSCL(P)_U
32-bit unsigned binary
ANY32_U
EN
Execution condition
Bit
BOOL
ENO
Execution result
Bit
BOOL
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
X, Y, M, L, SM,
F, B, SB, S
T, ST, C, D, W,
SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s1)
(s2)
(d)
(s1) (s2)
(d)
EN
ENO
d
s1
s2
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......