450
8 APPLICATION INSTRUCTION
8.8 Character String Operation Instruction
Converting 32-bit binary data to character string
DSTR(P)(_U)
These instructions add a decimal point to the 32-bit binary data in the device specified by (s2) at the location specified by (s1),
convert the data to character string data, and store the converted data in the device areas specified by (d) and later.
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
*1 T, ST, C cannot be used.
Ladder diagram
Structured text
ENO:=DSTR(EN,s1,s2,d);
ENO:=DSTRP(EN,s1,s2,d);
ENO:=DSTR_U(EN,s1,s2,d);
ENO:=DSTRP_U(EN,s1,s2,d);
FBD/LD
Operand
Description
Range
Data type
Data type (label)
(s1)
DSTR(P)
Head device number where the number of digits
of the conversion target data is stored
16-bit signed binary
ANY16_S_ARRAY
(Number of elements: 2)
DSTR(P)_U
16-bit unsigned binary
ANY16_U_ARRAY
(Number of elements: 2)
(s2)
DSTR(P)
Conversion target data
-2147483648 to +2147483647
16-bit signed binary
ANY32_S
DSTR(P)_U
0 to 4294967295
16-bit unsigned binary
ANY32_U
(d)
Head device number for storing the converted
data
Character string
ANYSTRING_SINGLE
EN
Execution condition
Bit
BOOL
ENO
Execution result
Bit
BOOL
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
X, Y, M, L, SM,
F, B, SB, S
T, ST, C, D, W,
SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s1)
(s2)
(d)
(s1) (s2)
(d)
EN
ENO
d
s1
s2
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......