2
Wiring
NPN output encoders can also be used.
Encoder
Phase A
Phase B
Phase Z
OUT
COM
E
OUT
COM
E
OUT
COM
E
φ
A
φ
B
PRESET
DISABLE
START
+24V
COM
Shielding wire
Shielding wire
Shielding wire
Shielding wire
φ
A24
φ
A12
φ
A5
COMA
φ
B24
φ
B12
φ
B5
COMB
XP24
XP5
COMP
XD24
XD5
COMD
3.3k
1.5k
0.5k
0.1k
0.1k
1.5k
0.5k
12 to 24V inputtable
12 to 24V
inputtable
DC24V+
YHP
YHN
DC24-
DC24V+
YSP
YSN
DC24-
*1
*1
*1
*1
〈〈〈〈〈
Using the solderless termination
〉〉〉〉〉
●
Use crimp terminals of the dimensions specified in the left figure.
●
Secure the terminals using a tightening torque of 0.5 to 0.8 N•m (5
to 8 kg•cm).
●
Wire only to the module terminals discussed in this manual. Leave
all thers vacant.
6.8 mm
(0.27 inches)
or less
6.8 mm
(0.27 inches)
or less
Class 3
grounding
(<100
Ω
)
Extension
cable
FX-1HC
PC
+24V
0V
SG
+24V
0V
External power source
DC12 to 24V
*1. Do not connect YHP and
YHN, or YSP and YSN
together.
*2. Connect SG and the gro-
unded terminal at the PC
side as required.
External power source
DC5V, 12V, 24V
*2
For M3.5
(0.14 inches)