background image

HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

7. Change and adjustment method of input/output characteristic

7.1 Change in input/output characteristic

At shipment, 0 to 250 range selected for 0 to 10V DC input/output.
When using an FX

0N

-3A for current input/output or differing voltage input/output except 0 to 10V DC, it is

necessary to readjust the offset and gain.
The module does not allow different input characteristics for two channels. 
Set analog values from 0 to 250 digital equivalent within the range specified in the table below when
changing the input/output characteristic. 

Range of allowance of input/output characteristic

Resolution changes depending on the set value when the input/output characteristic is changed. 
Example: Resolution becomes (5 to 0V)/250=20mV at voltage input 0 to 5V/0 to 250. 
Overall accuracy does not change. (Voltage input

±

0.1V, Current input: 

±

0.16mA)

7.2 Method of Calibration(A/D)

Both analog input channels share the same ‘setup’ and configuration. Hence only one channel needs to
be selected to perform the calibration for both analog input channels.
Use the following program and the appropriate wiring configuration to calibrate input channel 1 (and 
indirectly channel 2) of the FX

0N

-3A.

7.2.1 Input Calibration Program

7.2.2 Calibrating the Offset

1) Run the previously detailed program. Ensure X02 is ON.

2) Generate an offset voltage/current (in accordance with the analog operation range to be selected, see

table below) using the selected generator or analog output.

3) Adjust the A/D OFFSET potentiometer (‘pot’) until a digital value of 1 is read in D00.

Note : Turn the ‘pot’ clockwise and the digital value will increase. The ‘pot’ requires 18 revolutions to 

move between the minimum and maximum settings.

7.2.3 Calibrating the Gain

1) Run the previously detailed program. Ensure X02 is ON.

2) Generate a gain voltage/current (in accordance with the analog operation range to be selected, see

table below) using the selected generator or analog output.

3) Adjust the A/D GAIN potentiometer (‘pot’) until a digital value of 250 is read in D00.

Note 1: Turn the ‘pot’ clockwise and the digital value will increase. The ‘pot’ requires 18 revolutions to

move between the minimum and maximum settings.

Note 2: When necessary to maximize the 8 bit resolution, the digital value used in the gain adjustment

(detailed above) should be replaced with 255. This section has been written to demonstrate 250
full scale calibration.

Voltage

input

Current

input

Voltage

output

Current

output

Analog value when digital value is 0

0 to 1V

0 to 4mA

0V

4mA

Analog value when digital value is 250

5 to 10V

20mA

5 to 10V

20mA

Analog input range

0-10V DC

0-5V DC

4-20mA DC

Offset calibration value

0.040V

0.020V

4.064mA

Analog input range

0-10V DC

0-5V DC

4-20mA DC

Gain calibration value

10.000V

5.000V

20.000mA

P

O

W

E

R

D

/A

G

A

IN

A

/D

O

FF

S

E

T

A

/D

G

A

IN

D

/A

O

FF

S

E

T

V I N 2

C O M 2

C O M 1

I I N 1

I I N 2

V I N 1

V

+

+

P

O

W

E

R

D

/A

G

A

IN

A

/D

O

FF

S

E

T

A

/D

G

A

IN

D

/A

O

FF

S

E

T

V

I N

2

C O M 2

C O M 1

I

I N

1

I

I N

2

V

I N

1

C O M

V

V

O U T

I

O U T

+

P

O

W

E

R

A

/D

O

FF

S

E

T

A

V I N 2

C O M 2

C O M 1

I I N 1

I I N 2

V I N 1

+

P

O

W

E

R

D

/A

G

A

IN

A

/D

O

FF

S

E

T

A

/D

G

A

IN

D

/A

O

FF

S

E

T

A

V I N 2

C O M 2

C O M 1

I I N 1

I I N 2

V I N 1

C O M

V

O U T

I

O U T

+

V o l t m e t e r

C u r r e n t   g e n e r a t o r

A / D   G A I N  

D / A   O F F S E T  

D / A   G A I N

V o l t a g e   g e n e r a t o r

E x t e r n a l

v o l t a g e

i n p u t

I n t e g r a l

v o l t a g e

i n p u t

E x t e r n a l

c u r r e n t

i n p u t

I n t e g r a l

c u r r e n t

i n p u t

A m m e t e r

A / D   O F F S E T

TO

K0

K17

H00

K1

K0

K17

H02

K1

K0

K0

D0

K1

TO

X02

FROM

7.3 Method of Calibration(D/A)

Use the following program and the appropriate wiring configuration to calibrate the output channel of the
FX

0N

-3A

7.3.1 Output Calibration Program

7.3.2 Calibrating the Offset

1) Run the previously detailed program. Ensure X00 is ON and X01 is OFF.

2) Adjust the D/A OFFSET potentiometer (‘pot) until the selected meter displays the appropriate offset

voltage/current (in accordance with the analog operation range selected, see table below).

Note: Turn the ‘pot’ clockwise and the analog output signal will increase. The ‘pot’ requires 18 revolutions

to move between the minimum and maximum settings.

7.3.3 Calibrating the Gain

1) Run the previously detailed program. Ensure X00 is OFF and X01 is ON.

2) Adjust the D/A GAIN potentiometer (‘pot’) until selected meter displays the appropriate gain voltage/

current (in accordance with the analog operation range selected, see table below).

Note 1: Turn the ‘pot’ clockwise and the analog output signal will increase. The ‘pot’ requires 18

revolutions to move between the minimum and maximum settings

Note 2: When it is necessary to maximize the 8 bit resolution, the digital value used in the gain adjustment

(detailed above) should be replaced with 255. This section has been written to demonstrate a 250
full scale calibration.

8. Program example

8.1 Using Analog Inputs

The buffer memories (BFM) of the FX

0N

-3A are written TO or read FROM by the host PLC. The following

program reads the analog input from channel 1 of the FX

0N

-3A when M0 is ON, and the analog input data

of channel 2 when M1 is ON.

(H00) is written to BFM#17, selecting A/D input channel 1.
(H02) is written to BFM#17 starting the A/D conversion process for
channel 1.
BFM#0 is read, storing the current value of channel 1 in register
D00
(H01) is written to BFM#17 now selecting A/D input channel 2.
(H03) is written to BFM#17 to re-start the A/D conversion process,
but for channel 2.
BFM#0 is read, storing the current value of channel 2 in register
D01.

The time T

AD

 required to read an analog input channel is calculated as follows:

T

AD

 = (TO instruction processing time) 

×

 2 + (FROM instruction processing time)

Note : The 3 (TO/FROM) command format shown above should always be used when reading data from

the FX

0N

-3A’s analog input channels.

Analog output range

0-10V DC

0-5V DC

4-20mA DC

Offset calibration meter value

0.040V

0.020V

4.064mA

Analog 

output range

0-10V DC

0-5V DC

4-20mA DC

Gain calibration meter value

10.000V

5.000V

20.000mA

D/A

GAIN

A/D

GAIN

D/A

OFFSET

V

CO
M

V

OU
T

I

OU
T

+

D/A

GAIN

A/D

GAIN

D/A

OFFSET

A

CO
M

V

OU
T

I

OU
T

+

Voltage

output

Current

output

Voltmeter

Ammeter

TO

K0

K16

K1

K1

K0

K17

H04

K1

K0

K17

H00

K1

TO

X00

TO

X01

TO

K0

K16 K250

K1

K0

K17

H04

K1

K0

K17

H00

K1

TO

TO

X00

X01

TO

K0

K17

H00

K1

K0

K17

H02

K1

FROM

K0

K0

D00

K1

TO

TO

K0

K17

H01

K1

K0

K17

H03

K1

FROM

K0

K0

D01

K1

TO

M0

M1

8.2 Using Analog Outputs

The buffer memories (BFM) of the FX

0N

-3A are written TO, or read FROM by the host PLC. In the

following program, when M0 is turned ON the D/A conversion process is executed and an analog signal
equivalent to the digital value stored in this example, is output to register D02

The contents of D2 are written to BFM#16. This will be converted to
an analog output.
(H04) is written to BFM#17 to start the D/A conversion process.

The time T

AD

 required to write an analog input channel is calculated as follows:

T

AD

 = (TO instruction processing time) 

×

 3

Note : The 3 (TO) instruction format shown above should always be used when writing data to the

FX

0N

-3A’s analog output channel.

Details on both the FROM and TO instructions (functions 78 and 79 respectively) can be found in the
“FX series Programming Manual (

ΙΙ

)”

8.3 Using FX

1N

, FX

2N

 (V3.00 or more) or FX

2NC

 (V3.00 or more) Series PLC’s

Please use FNC 176 (RD3A) and FNC 177 (WR3A)
Refer to FX Series Programming Manual 

ΙΙ

.

9. Error Checking

If the FX

0N

-3A special function block does not seem to operate normally, check the following items:

Check the status of POWER LED.
Lit: The extension cable is properly connected.
Otherwise: Check the connection of the extension cable.

Check the external wiring.

Check whether the output load connected to the analog output terminal is within the following 
specified limits.
Voltage output: 1k

Ω 

to 1M

Ω

, Current output: 500

Ω 

or less

Check whether the impedance of the input device is within the specified limits.
Voltage input: 200k

Ω

, Current input: 250

Ω

.

Check the calibration of the FX

0N

-3A’s analog channels (input and output) using a voltmeter/ ammeter 

as required. See previous two sections for a detailed explanation.

TO

K0

K16

D02

K1

K0

K17

H04

K1

K0

K17

H00

K1

TO

M0

TO

Guidelines for the safety of the user and protection of the FX

0N

-3A Special 

function block

This manual has been written to be used by trained and competent personnel. This is defined
by the European directives for machinery and EMC.

If in doubt at any stage during the installation of the FX

0N

-3A always consult a professional

electrical engineer who is qualified and trained to the local and national standards. If in doubt
about the operation or use of the FX

0N

-3A please consult the nearest Mitsubishi Electric

distributor. 

Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment. 

All examples and diagrams shown in this manual are intended only as an aid to understanding
the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual
use of the product based on these illustrative examples. 

Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.

Manual number : JY992D49001

Manual revision : F

Date

: April 2015

JY992D49001F

Effective April 2015

Specifications are subject to 
change without notice

Summary of Contents for MELSEC-F FX0N-3A

Page 1: ...ox 25V rating at position 2 P O W E R D A G A I N A D O F F S E T A D G A I N D A O F F S E T P O W E R V I N 2 C O M 2 C O M 1 I I N 1 I I N 2 V I N 1 V I N 2 C O M C O M I I N 1 I I N 2 V I N 1 C O M V O U T I O U T C O M V O U T I O U T 3 5 m m D I N r a i l g r o o v e 9 0 3 5 8 7 3 4 3 M o u n t i n g h o l e 2 h o l e s 4 5 0 1 8 d i a 4 3 1 6 9 4 0 1 6 8 0 3 1 5 9 0 3 5 4 M 3 0 1 2 t e r m ...

Page 2: ... power requirement 24V DC 10 90mA internal power supply from main unit Digital circuit power requirement 5V DC 30mA internal power supply from main unit Isolation Photo coupler isolation between analog and digital circuit No isolation between analog channels Number of occupied I O points 8 I O points from expansion bus either input or output Voltage input Current input Analog input range At shipme...

Page 3: ...t status will operate in the following manner Status change of the host PLC RUN Ö STOP The last operational value used by the analog output channel during RUN operation is retained during STOP mode STOP Ö RUN Once the host PLC is switched back into RUN mode the analog output reacts as normal to the program controlled digital values PLC power shutdown The analog output signal ceases operation e Rem...

Page 4: ...igital value used in the gain adjustment detailed above should be replaced with 255 This section has been written to demonstrate 250 full scale calibration Voltage input Current input Voltage output Current output Analog value when digital value is 0 0 to 1V 0 to 4mA 0V 4mA Analog value when digital value is 250 5 to 10V 20mA 5 to 10V 20mA Analog input range 0 10V DC 0 5V DC 4 20mA DC Offset calib...

Page 5: ...alog input data of channel 2 when M1 is ON H00 is written to BFM 17 selecting A D input channel 1 H02 is written to BFM 17 starting the A D conversion process for channel 1 BFM 0 is read storing the current value of channel 1 in register D00 H01 is written to BFM 17 now selecting A D input channel 2 H03 is written to BFM 17 to re start the A D conversion process but for channel 2 BFM 0 is read sto...

Page 6: ...tion block does not seem to operate normally check the following items Check the status of POWER LED Lit The extension cable is properly connected Otherwise Check the connection of the extension cable Check the external wiring Check whether the output load connected to the analog output terminal is within the following specified limits Voltage output 1kΩ to 1MΩ Current output 500Ω or less Check wh...

Page 7: ...terminals Analog circuit power requirement 24V DC 10 90mA internal power supply from main unit Digital circuit power requirement 5V DC 30mA internal power supply from main unit Isolation Photo coupler isolation between analog and digital circuit No isolation between analog channels Number of occupied I O points 8 I O points from expansion bus either input or output Voltage input Current input Anal...

Page 8: ... The pot requires 18 revolutions to move between the minimum and maximum settings Note 2 When it is necessary to maximize the 8 bit resolution the digital value used in the gain adjustment detailed above should be replaced with 255 This section has been written to demonstrate a 250 full scale calibration 8 Program example 8 1 Using Analog Inputs The buffer memories BFM of the FX0N 3A are written T...

Reviews: