  3. NAME OF EACH PART 

 

 
The name of each part in the AJ65SBT-64AD is shown. 

 

 

 

 

Number 

Name and 

appearance 

Description 

1) 

Operation 
status 
display LED 

PW LED 

ON   : Power supply on 
OFF : Power supply off 

RUN LED 

Normal 
mode 

On 

: Normal operation 

Flashing : 0.1s intervals indicate an input range error. 
Off 

: 24VDC power supply shutoff or watchdog timer 

error occurred. 

Test  
mode 

On 

: Indicates that the SELECT/SET switch is in the 

SET position. 

Flashing : 0.1s intervals indicate that the input range 

setting is not any of "user range settings 1 to 3". 
0.5s intervals indicate that you attempted to 
make offset/gain setting outside the setting 
range. 

Off 

: Indicates that the SELECT/SET switch is in the 

SELECT or center position. 

L RUN 
LED 

On  : Normal communication 
Off  : Communication cutoff (time expiration error) 

L ERR. 
LED 

On  : Indicates that transmission speed setting or station number 

setting is outside the range. 

Flicker at fixed intervals 

:  Indicates  that  transmission  speed 

setting or station number setting was 
changed from that at power-on. 

Flicker at unfixed intervals : Indicates that you forgot fitting the 

termination resistor or the module or 
CC-Link dedicated cable is affected 
by noise. 

Off  : Indicates normal communications. 

 

 

 

Summary of Contents for MELSEC AJ65SBT-64AD

Page 1: ...you for buying the programmable controller MELSEC Series Prior to use please read both this manual and detailed manual thoroughly and familiarize yourself with the product MODEL AJ65S 64AD U H JE MODEL CODE 13JT09 IB NA 0800138 K 2102 MEE 2000 MITSUBISHI ELECTRIC CORPORATION ...

Page 2: ...r or moderate injury or property damage Under some circumstances failure to observe the precautions given under CAUTION may lead to serious consequences Observe the precautions of both levels because they are important for personal and system safety Make sure that the end users read this manual and then keep the manual in a safe place for future reference Design Precautions WARNING In the case of ...

Page 3: ...t Ground the FG and FG1 terminals to the protective ground conductor dedicated to the programmable controller Failure to do so may result in malfunction Tighten any unused terminal screws within the specified torque range 0 42 to 0 50N m Failure to do so may cause a short circuit due to contact with a solderless terminal Use applicable solderless terminals and tighten them within the specified tor...

Page 4: ...e or retightening the terminal screws Failure to do so may cause the module to fail or malfunction Undertightening the terminal screws can cause short circuit or malfunction Overtightening can damage the screw and or module resulting in drop short circuit or malfunction Do not disassemble or modify the modules Doing so may cause failure malfunction injury or a fire Do not drop or apply strong shoc...

Page 5: ...nes circonstances le non respect d une précaution de sécurité introduite sous le titre ATTENTION peut avoir des conséquences graves Les précautions de ces deux niveaux doivent être observées dans leur intégralité car elles ont trait à la sécurité des personnes et aussi du système Veiller à ce que les utilisateurs finaux lisent ce manuel qui doit être conservé soigneusement à portée de main pour s ...

Page 6: ...recte peut être à l origine de dysfonctionnements ou de pannes du module Pécautions de câblage ATTENTION Couper l alimentation externe du système sur toutes les phases avant de commencer à câbler Faute quoi le produit risquerait d être endommagé Toujours mettre à la masse la borne FG sur le conducteur de protection de terre Faute de quoi cela peut entraîner un dysfonctionnement Serrer les vis des ...

Page 7: ... dysfonctionnement Les câbles doivent être placés dans un conduit de câbles ou doivent être attachés Faute de quoi le ballottement ou le déplacement des câbles pourrait endommager le module ou les câbles et être à l origine de dysfonctionnements par mauvais contact Ne pas entremêler les lignes de commandes ou câbles de communication avec les lignes des circuits principaux ou les câbles d alimentat...

Page 8: ... ou dysfonctionnements et être à l origine de blessures ou de départs de feu Ne pas faire tomber le module et ne pas le soumettre à des chocs Cela risquerait d endommager le module Avant d installer ou retirer le module du tableau couper l alimentation externe du système sur toutes les phases Le non respect de cette précaution peut être à l origine de pannes ou de dysfonctionnements du module Aprè...

Page 9: ...se of the PRODUCT in Nuclear Power Plants and any other power plants operated by Power companies and or any other cases in which the public could be affected if any problem or fault occurs in the PRODUCT Railway companies or Public service purposes and or any other cases in which establishment of a special quality assurance system is required by the Purchaser or End User Aircraft or Aerospace Medi...

Page 10: ...struction Chapter 1 Section 2 1 2 2 5 2 Chapter 7 Mar 2006 IB NA 0800138 D Partial correction Section 2 3 Sep 2006 IB NA 0800138 E Partial correction SAFETY PRECAUTIONS Chapter 3 Chapter 7 Dec 2006 IB NA 0800138 F Partial correction Chapter 6 Oct 2008 IB NA 0800138 G Partial correction SAFETY PRECAUTIONS Compliance with the EMC and Low Voltage Directives Section 2 1 2 2 4 1 6 1 Deletion Section 5 ...

Page 11: ...orrection Chapter 2 Section 2 2 4 1 5 1 6 2 Chapter 3 7 Feb 2021 IB NA 0800138 K Correction Section 2 2 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in thi...

Page 12: ...al No Model code Analog Digital Converter Module Type AJ65SBT 64AD User s Manual SH 080106 13JR18 COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES 1 Method of ensuring compliance To ensure that Mitsubishi programmable controllers maintain EMC and Low Voltage Directives when incorporated into other machinery or equipment certain measures may be necessary Please refer to one of the following manuals U...

Page 13: ...o 150Hz 9 8m s2 Under continuous vibration 5 to 8 4Hz 1 75mm 8 4 to 150Hz 4 9m s2 Shock resistance Compliant with JIS B 3502 and IEC 61131 2 147 m s2 3 times each in 3 directions X Y Z Operating atmosphere No corrosive gases Operating altitude 3 0 to 2000m Installation location Inside a control panel Overvoltage category 1 II or less Pollution degree 2 2 or less 1 This indicates the section of the...

Page 14: ...grammable controller under pressure higher than the atmospheric pressure of altitude 0m Doing so may cause malfunction When using the programmable controller under pressure please consult your local Mitsubishi Electric representative ...

Page 15: ...upied stations 1 station Communication cable CC Link dedicated cable Dielectric withstand voltage Between power supply communication system batch and analog input batch 500VAC 1 minute Isolation system Between communication system terminals and all analog input terminals Digital isolator Between power supply system terminals and all analog input terminals Photocoupler Between channels Non isolatio...

Page 16: ...f heating within approx 30 minutes after power is turned ON 1 Digit indicates digital value 2 Current value indicates value of instant input current that does not break module inner electrical resistance 2 3 Checking hardware versions The hardware versions of the AJ65SBT 64AD can be checked on the DATE section on the rating plate which is situated on the side of the module MODEL POWER DATE MADE IN...

Page 17: ...user range settings 1 to 3 0 5s intervals indicate that you attempted to make offset gain setting outside the setting range Off Indicates that the SELECT SET switch is in the SELECT or center position L RUN LED On Normal communication Off Communication cutoff time expiration error L ERR LED On Indicates that transmission speed setting or station number setting is outside the range Flicker at fixed...

Page 18: ...s 40 20 10 8 4 2 1 1 OFF OFF OFF OFF OFF OFF ON 2 OFF OFF OFF OFF OFF ON OFF 3 OFF OFF OFF OFF OFF ON ON 4 OFF OFF OFF OFF ON OFF OFF 10 OFF OFF ON OFF OFF OFF OFF 11 OFF OFF ON OFF OFF OFF ON 64 ON ON OFF OFF ON OFF OFF Example To set the station number to 32 set the switches as indicated below Station number Tens Units 40 20 10 8 4 2 1 32 OFF ON ON OFF OFF ON OFF 5 Transmission speed setting swi...

Page 19: ...ation environment Never install the A series programmable controller in the following environments 1 Locations where the ambient temperature is outside the range of 0 to 55 C 2 Locations where the ambient humidity is outside the range of 10 to 90 RH 3 Locations where dew condensation takes place due to sudden temperature changes 4 Locations where there are corrosive and or combustible gasses 5 Loc...

Page 20: ...O module etc Côté module d entrée sortie Terminating resistor Résistance d extrémité CC Link dedicated cable Câble dédié pour CC Link Blue Bleu White Blanc Yellow jaune DA DB DG SLD FG DA DB DG SLD FG DA DB DG SLD FG Terminal resistor Terminal resistor Master module AJ65SBT 64AD I O module etc CC Link dedicated cable CC Link dedicated cable Blue White Yellow Blue White Yellow Blue White Yellow Blu...

Page 21: ...rammable controller Noises surges or conductivity may affect the system 3 Place a one point grounding on the programmable controller side for the shielded line or shielded cable However depending on the external noise conditions it may be better have a grounding externally 6 2 Module connection example English French For voltage input Pour entrée de tension Signal source 0 to 10 V Source de signal...

Page 22: ... perform the setting of the offset gain values again 1 Utilisez une ligne blindée à torsion double base pour le câble d alimentation 2 Indique la résistance d entrée AJ65SBT 64AD 3 Pour l entrée de courant le raccordement doit se faire aux bornes V et I 4 En cas de bruit ou d ondulation sur le câble externe connectez un condensateur d environ 0 1 à 0 47 µF produit résistant à une tension de 25 V o...

Page 23: ...AD I V COM SLD TEST I V I V TEST SELECT PWRUN 234OFFSET GAIN FG I V AG SLD COM FG1 SET CH3 CH2 CH1 4 STATION NO 1 B RATE 1 2 2 4 8 10 20 40 CH4 ON 7 5 7 9 4 50 16 5 40 4 5 4 5 COM COM 2 4 5 5 1 installation hole M4 installation screw DIN rail center About 105 PW RUN L RUNL ERR CH1 2 OFFSETGAIN MITSUBISHI AJ65S BT 64AD DA DG 24V 24G DB SLD FG TEST TEST V I AG V I CH1 CH2 SE LECT SE T STATION NO B R...

Page 24: ...12 MEMO ...

Page 25: ...13 MEMO ...