JEP0-IL9416
24
D - 2 Specifying operation indicator LED hold (Item No. : “860” range)
Select operation indicator LEDs to be held or reset according to the operation indicator LED hold data
shown in the instruction manual specifically prepared for the model.
<< Example >> To change the setting for the operation indicator LEDs of the earth fault time-delayed and
instantaneous elements from self hold to automatic reset:
Currently used specification
(factory default setting)
Target specification
Operation indicator LEDs to be
automatically reset
None
Earth fault time-delayed and earth fault
instantaneous
Operation indicator LED hold
data
01FF 00EF
To get the operation indicator LED hold data, first give a desired value for each setting item to which a
digit number is allocated as listed in the operation indicator LED hold data setting table shown below.
This will make up a 16-digit binary code. Then, convert the binary code into a 4-digit hexadecimal code.
Note that the arrangement shown in the table below varies by model. Please refer to the instruction
manual specifically prepared for the model.
Input
Digit
No.
Setting item
0 1
0
Trip
Reset
Hold
1
Phase fault time-delayed A-phase
Reset
Hold
2
Phase fault time-delayed B-phase
Reset
Hold
3
Phase fault time-delayed C-phase
Reset
Hold
4
Earth fault time-lag
Reset
Hold
5
Phase fault instantaneous A-phase
Reset
Hold
6
Phase fault instantaneous B-phase
Reset
Hold
7
Phase fault instantaneous C-phase
Reset
Hold
8
Earth fault instantaneous
Reset
Hold
9
Not used
×
10
Not used
×
11
Not used
×
12
Not used
×
13
Not used
×
14
Not used
×
15
Not used
×
0
0
0
0
0 0
1
1
1
0
0
1
1
1
1
0
ditto.
E
ditto.
0
Operation indicator LED hold data
0
Conversion from binary number to hexadecimal
Binary
Æ
Hexadecimal
Binary
Æ
Hexadecimal
Binary
Æ
Hexadecimal
0 0 0 0
Æ
0
0 1 1 0
Æ
6
1 1 0 0
Æ
C
0 0 0 1
Æ
1
0 1 1 1
Æ
7
1 1 0 1
Æ
D
0 0 1 0
Æ
2
1 0 0 0
Æ
8
1 1 1 0
Æ
E
0 0 1 1
Æ
3
1 0 0 1
Æ
9
1 1 1 1
Æ
F
0 1 0 0
Æ
4
1 0 1 0
Æ
A
0 1 0 1
Æ
5
1 0 1 1
Æ
B
ditto.
F