16
Check of indoor electronic control P.C. board
C
The unit does not operate with the remote controller.
Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
Replace the fuse.
Trouble of the indoor electronic
control P.C. board.
Replace the varistor.
Yes
Check both “parts side”and “pattern
side” of indoor electronic control P.C.
board visually.
No
Is varistor(NR11)burnt?
Yes
Is fuse(F11)blown?
Check of indoor electronic control P.C. board
D
When OPERATION INDICATOR lamp flashes 4 - time.
Indoor unit does not operate.
Turn off the power supply.
Replace the indoor electronic
control P.C. board.
No
Be sure to check both fuse
and varistor in any case.