9-3. Troubleshooting check table
❈
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.
Self check table
9-2. Instruction of troubleshooting
OPERATION INDICATOR
lamp
Start
Indoor unit
operates.
Outdoor unit
doesn't
operate.
Indoor unit
doesn't
receive the
signal from
remote
controller.
OPERATION
INDICATOR
lamp on the
indoor unit is
flashing
on and off.
Outdoor unit
operates only
in Test Run
operation.
w
1
Outdoor unit
doesn't
operate
even in
Test Run
operation.
w
1
Indoor unit
operates, when
the
EMERGENCY
OPERATION
switch is
pressed.
Indoor unit
doesn't
operate,
when the
EMERGENCY
OPERATION
switch is
pressed.
Check room
temperature
thermistor.
Refer to 9-6.
"Test point
diagram and
voltage".
Check of
wiring
diagram of
outdoor
unit.
w
2
Refer to 9-5.
B
"Check of
remote
controller
and receiver
P.C. board".
Refer to 9-5.
C
"Check of
indoor
electronic
control
P.C. board".
2-time flash
Cause:
Indoor unit
• Trouble of
room
temperature/
indoor coil
thermistor
Check room
tempreture
thermistor and
indoor coil
thermistor.
Refer to 9-6.
"Test point
diagram and
voltage".
When the
remote
controller is
pressed
or when the
EMERGENCY
OPERATION
switch is
pressed,
the fan doesn't
rotate, with
OPERATION
INDICATOR
lamp on.
Refer to 9-5.
A
"Check of
indoor fan
motor".
Refer to outdoor unit service manual.
w
2 Before checking the outdoor unit, make sure if
any signal or power is being transmitted from
the indoor unit.
4-time flash
Cause:
Indoor unit
• Trouble of
indoor unit
control
system
Replace the
indoor
electronic
control
P.C. board.
w
1."Test Run operation" means the operation within 30 minutes after
EMERGENCY OPERATION switch is pressed.
No.
1
Symptom
Operation indicator lamp
Detection method
Checkpoint
Indoor coil
thermistor
Abnormal
point
Room
temperature
thermistor
2-time flash
2.5-second OFF
Detect Indoor coil/room temperature
thermistor short or open circuit.
• Check the resistance of
thermistor.
• Reconnect the connector.
• Check the indoor electronic
control P.C.
Outdoor unit
does not
operate.
2
4-time flash
2.5-second OFF
Indoor
control
system
When it cannot properly read data in the
nonvolatile memory of the indoor electronic
control P.C. board.
Outdoor unit
does not
operate.
• Check the indoor electronic
control P.C. board.
OB382A.qxp 06.5.9 6:42 PM Page 11