4-2 If used together with MELANS.
SW1-2 [ON]
E
SW2-1 [ON]
Shielded wire ground
Centralized controller
(MELANS)
Power supply unit
M-NET transmission line
(Centralized control line)
M-NET address 201 to 250 [factory setting 247]
(* Setting of position 100 not required.)
(Note:1) When connecting LOSSNAY, register the sequence must be registered from the shared MELANS.
(Note 2) When changing the system configuration, such as the M-NET address, MELANS being shared must be
registered or changed.
(Note 3) Refer to the “System Design and Construction Manual” for the outdoor unit for details on the M-NET wiring length.
(Note 4) Set the M-NET address so that it is not duplicated with other units.
ON
OFF
1
2
3
4
5
6
7
8
9 10
ON
OFF
1
2
3
4
5
6
7
8
9 10
ON
OFF
1
2
3
4
5
6
7
8
9 10
Factory setting
247
CN41
OFF
OFF
CN41
M-NET address of LM-AP
LM-AP power switch connector
Combined switch for LM-AP MALANS
OC central control (SC) on/off switch
OC power supply connector
SWU2, 1 [201 to 250]
CN411 as is (power not supplied)
SW1 - 2 [ON] (Used together with MELANS)
SW2 -1 [ON] (Central control)
CN41 as is (power not supplied)
Item
Setting
SW2-1 [OFF]
as is
❇
OC : Outdoor Unit
: Switch Position
M-NET transmission line
(Indoor/outdoortransmission line)
M-NET transmission line
(Indoor/outdoortransmission line)
LM-AP
TB2
CN41
CN41
TB7
TB3
TB7
TB3
OC
OC
as is
as is
CN41