background image

Left or left-rear piping

Note:

Be sure to reattach the drain 
hose and the drain cap in case 
of left or left-rear piping.
Otherwise, it could cause drops 
of water to drip down from the 
drain hose.

1) Put the refrigerant piping and the drain hose together, 

then firmly apply felt tape (7) from the end. 

  Felt tape (7) overlap width should be 1/3 the tape width. 

Use a bandage stopper at the end of felt tape (7).

2) Pull out the drain cap at the rear right of the indoor unit. 

(Fig. 1)
• Hold the convex section at the end and pull the drain 

cap.

3) Pull out the drain hose at the rear left of the indoor unit. 

(Fig. 2)
• Hold the claw marked by the arrows and pull out the 

drain hose forward.

4) Put the drain cap into the section to which the drain 

hose is to be attached at the rear of the indoor unit.  
(Fig. 3)
• Insert not sharp-edged tools such as screwdrivers into 

the hole at the end of the cap and insert the cap fully 
into the drain pan.

5) Insert the drain hose fully into the drain pan at the rear 

right of the indoor unit. (Fig. 4)
• Check if the hose is hooked securely to the projection 

of its inserting part at the drain pan.

6) Insert the drain hose into wall hole sleeve (C), and hook 

the upper part of indoor unit on installation plate (1). Then, 
move the indoor unit completely to the left in order to make 
placing the piping in the back space of the unit easier.

7) Cut out a piece of cardboard from the shipping box, roll 

it up, hook it onto the back rib, and use it as a spacer to 
lift the indoor unit. (Fig. 5)

8) Connect the refrigerant piping with the extension pipe 

(B).

9) Thrust the lower part of the indoor unit into the installation 

plate (1).

3-2. FLARING WORK

1) Cut the copper pipe correctly with pipe cutter.  

(Fig. 1, 2)

2)  Completely remove all burrs from the cut cross section 

of pipe. (Fig. 3)
•  Put the end of the copper pipe to downward direction 

as you remove burrs in order to avoid to let burrs 
drop in the piping.

3) Remove flare nuts attached to indoor and outdoor 

units, then put them on pipe having completed burr 
removal. (Not possible to put them on after flaring 
work.) 

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the 

dimension shown in the table. Select A mm from the 
table according to the tool you use.

5) Check 

•  Compare the flared work with Fig. 6.
•  If flare is noted to be defective, cut off the flared sec-

tion and do flaring work again.

3-3. PIPE CONNECTION

•  Fasten flare nut with a torque wrench as specified in the table.
•  When fastened too tight, flare nut may break after a long period and cause refrigerant leak-

age.

•  Be sure to wrap insulation around the piping. Direct contact with the bare piping may result 

in burns or frostbite.

Indoor unit connection

Connect both liquid and gas pipings to indoor unit.
•  Apply a thin coat of refrigeration oil (J) on the seat surface of pipe.
•  For connection, first align the center, then tighten the first 3 to 4 turns of flare nut.
•  Use tightening torque table above as a guideline for indoor unit side union joint section, and 

tighten using two wrenches. Excessive tightening damages the flare section.

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the 
same manner applied for indoor unit.
•  For tightening, use a torque wrench or spanner and use the 

same tightening torque applied for indoor unit.

3-4. INSULATION AND TAPING

1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using piping tape (G), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (G) with tape (with adhesive agent attached).
•  When piping have to be arranged through above ceiling, closet or where the temperature 

and humidity are high, wind additional commercially sold insulation to prevent condensa-
tion.

Rear, right, or downward piping

1) Put the refrigerant piping and the drain hose 

together, then firmly apply piping tape (G) from 
the end.

2) Insert the piping and the drain hose into the wall 

hole sleeve (C), and hook the upper part of the 
indoor unit on the installation plate (1).

3) Check if the indoor unit is hooked securely on the installation plate (1) by moving 

the unit to left and right.

4) Thrust the lower part of the indoor unit into the installation plate (1).

Drain Piping

•  If the extension drain hose has to pass through a room, be sure to wrap it with com-

mercially sold insulation. 

•  The drain hose should point downward for easy drain flow. (Fig. 1)
•  If the drain hose provided with the indoor unit is too short, connect it with drain hose 

(I) that should be provided at your site. (Fig. 2)

•  When connecting the drain hose to the hard vinyl chloride pipe, be sure to insert it 

securely into the pipe. (Fig. 3)

Do not make drain piping as shown below.

Do not raise

Accumulated 
drain water

Air

Waving

Water 
leakage

Water 
leakage

Water 
leakage

Tip of drain 
hose dipped 
in water

Ditch

At least 
50 mm 
gap

Cut off in case of 
right piping.

Cut off in case of down-
ward piping.

Copper 
pipe

Good

90°

Tilted Uneven Burred

No good

Fig. 1

Fig. 2

Burr

Copper pipe

Spare reamer

Pipe cutter

Clutch type

Flaring tool

Fig. 4

Fig. 3

Downward 
slope

Drain 
hose

Soft hose 
I.D. 15 mm

Drain hose

Hard vinyl chloride 
pipe I.D. 30 mm

Insert  
securely

Different 
diameter 
joint

70 cm or 
more

Fig. 1

Fig. 2

Fig. 3

Drain cap

Drain cap

Drain hose

Cut off in case of left 
piping.

Drain cap

Piping tape (G)

Drain hose

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Felt tape (7)

3.  OUTDOOR UNIT INSTALLATION

Smooth all 
around

Even length 
all around

Inside is shin-
ing without any 
scratches.

A

Flare nut

Die

Fig. 5

Fig. 6

Copper pipe

Wing nut type

3-1. CONNECTING WIRES FOR OUTDOOR UNIT

1) Open the service panel.
2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from 

the indoor unit correctly on the terminal block. Be careful not to make mis-wiring. Fix 
the wire to the terminal block securely so that no part of its core is appeared, and no 
external force is conveyed to the connecting section of the terminal block. 

3) Firmly tighten the terminal screws to prevent them from loosening. After tightening, 

pull the wires lightly to confirm that they do not move.

4) Connect power supply cord (K).
5) Fix indoor/outdoor unit connecting wire (A) and power supply cord (K) with the cord clamp.
6) Close the service panel securely.

Terminal block

Cord clamp

L N

Power supply cord (K)

Indoor/outdoor unit 
connecting wire (A)

•  Make earth wire a little longer than 

others. (More than 100 mm)

•  For future servicing, give extra 

length to the connecting wires.

•  Be sure to attach each screw to 

its correspondent terminal when 
securing the cord and/or the wire 
to the terminal block.

15 mm

35 mm

Lead wire

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch type 

tool  

for R410A

Clutch type 

tool  

for R22

Wing nut 

type tool  

for R22

N•m

kgf•cm

ø6.35  (1/4”)

17

0 to 0.5

1.0 to 1.5

1.5 to 2.0

13.7 to 17.7 140 to 180

ø9.52  (3/8”)

22

34.3 to 41.2 350 to 420

ø12.7  (1/2”)

26

2.0 to 2.5

49.0 to 56.4 500 to 575

ø15.88  (5/8”)

29

73.5 to 78.4 750 to 800

 

WARNING

When installing the unit, securely connect the refrigerant 
pipes before starting the compressor.

Summary of Contents for JG79A476H01

Page 1: ...ab normally high This could cause the pipes to burst or injury N When installing the unit securely connect the refrigerant pipes before starting the compressor If the compressor is started before the refrigerant pipes are connected and when the stop valve is open air could be drawn in and the pressure in the refrigeration cycle could become abnormally high This could cause the pipes to burst or in...

Page 2: ...code requirements Liquid pipe Gas pipe Felt tape 7 Indoor outdoor unit connecting wire A Piping tape G Indoor unit Wall hole sleeve C Cut off the extra length Pipe fixing band E Be sure to use wall hole sleeve C to prevent in door outdoor connecting wire A from contacting metal parts in the wall and to prevent damage by rodents in case the wall is hollow Wall hole cover D Seal the wall hole gap wit...

Page 3: ... 3 Using piping tape G apply taping starting from the entry of outdoor unit Stop the end of piping tape G with tape with adhesive agent attached When piping have to be arranged through above ceiling closet or where the temperature and humidity are high wind additional commercially sold insulation to prevent condensa tion Rear right or downward piping 1 Put the refrigerant piping and the drain hose...

Page 4: ...sides of gas pipe and liquid pipe Operating without fully opening lowers the performance and this causes trouble Caution After test run or remote signal reception check turn off the unit with the E O SW or the remote controller before turning off the power supply Not doing so will cause the unit to start operation automatically when power supply is resumed To the user After installing the unit mak...

Reviews: