13 - 34
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
(2) Station information setting
: Necessary : As necessary : Not necessary
*1
When the [Mode] of the CC-Link module is set at [Remote
net - (Ver. 1 mode)], [Remote station points] cannot be set.
*2
Set the same setting as that of the GOT.
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU ether turning OFF and then ON
or resetting.
[Controller Setting] of GT Designer3
POINT
POINT
POINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
13.3.1 Setting communication interface
(Communication settings)
13.4.9 Connecting to MELSEC-L
series with CC-Link Ver.2
compatible
This section describes the settings of the GOT and
MELSEC-L in the following case of the system
configuration.
POINT
POINT
POINT
(1) CC-Link module (L Series)
For details of the CC-Link module (L Series), refer
to the following manual.
MELSEC-L CC-Link System Master/Local
Module User's Manual
(2) CC-Link function built-in CPU
For details on the CC-Link function built-in CPU,
refer to the following manual.
MELSEC-L CC-Link System Master/Local
Module User's Manual
System configuration
(Example when using CC-Link module (L Series))
Item
*1
Set value
Setting
necessity at
GOT
connection
Station type
Intelligent
device station (fixed)
Exclusive station count
*2
Exclusive station 1
Reserve/invalid station
select
No setting
Intelligent buffer select
(word)
(Use default value)
Item
Set value
Station No.
1: Station No.1
Transmission Rate
0: Online 156kbps
Mode
Ver.1: Remote net (Ver.1 mode)
Expanded Cyclic
Single (Use default value)
Number of stations occupied
1 Station
Input for Error Station
0: Clear
Retry
3times (Use default value)
Timeout Time
3sec (Use default value)
Delay Time
0ms (Use default value)
<CC-Link module>
*1
Type
: Master station
Station No.
: Station No.0
Mode
: Remote net (Ver.3 mode)
All connect count
: 1
Transmission speed : 156kbps
<GOT>
(Use the default value for settings other
than the following.)
Station type
: Intelligent device
station
Station No.
: Station No.1
Expanded cyclic setting : Single
Number of
stations occupied
: Exclusive station
Transmission speed
: 156kbps
(Use the default value for the settings other than the following.)
■
[Controller Setting] of GT Designer3
■
Summary of Contents for GT15
Page 2: ......
Page 34: ...A 32 ...
Page 92: ......
Page 110: ...2 18 2 DEVICE RANGE THAT CAN BE SET 2 9 MELSEC WS ...
Page 186: ...5 10 5 BUS CONNECTION 5 2 System Configuration ...
Page 218: ...5 42 5 BUS CONNECTION 5 4 Precautions ...
Page 254: ...6 36 6 DIRECT CONNECTION TO CPU 6 6 Precautions ...
Page 286: ...7 32 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 350: ...8 64 8 ETHERNET CONNECTION 8 5 Precautions ...
Page 368: ...9 18 9 MELSECNET H CONNECTION PLC TO PLC NETWORK 9 5 Precautions ...
Page 420: ...11 26 11 CC Link IE CONTROLLER NETWORK CONNECTION 11 5 Precautions ...
Page 440: ...12 20 12 CC Link IE FIELD NETWORK CONNECTION 12 5 Precautions ...
Page 490: ...13 50 13 CC Link CONNECTION INTELLIGENT DEVICE STATION 13 5 Precautions ...
Page 510: ......
Page 564: ...15 54 15 INVERTER CONNECTION 15 7 Precautions ...
Page 668: ......
Page 712: ...21 12 21 MULTIPLE GT14 GT12 GT11 GT10 CONNECTION FUNCTION 21 5 Precautions ...
Page 713: ...MULTI CHANNEL FUNCTION 22 MULTI CHANNEL FUNCTION 22 1 ...
Page 714: ......
Page 760: ...22 46 22 MULTI CHANNEL FUNCTION 22 5 Multi channel Function Check Sheet ...
Page 761: ...FA TRANSPARENT FUNCTION 23 FA TRANSPARENT FUNCTION 23 1 ...
Page 762: ......
Page 860: ...REVISIONS 4 ...
Page 863: ......